Digital outputs of the MASTER unit
Table 11.
#
DESCRIPTION COLD AIR TYPE
NO1
COMPRESSOR stage 1 /
VENTILATOR
NO6
PUMP
NO8
N/A
Analog inputs of the SLAVE unit
Table 12.
#
DESCRIPTION COLD AIR TYPE
B1
INJECTION TEMPERATURE
B2
RETURN TEMPERATURE
B3
SUCTION
B4
CONDENSER TEMPERATURE
Digital inputs of the SLAVE unit
Table 13.
#
DESCRIPTION COLD AIR TYPE
DI1
HIGH PRESSURE
DI2
LOW PRESSURE
DI3
EVAPORATOR FLOW
DI4
PHASE MOTOR PROTECTOR
Digital outputs of SLAVE unit
Table 14.
Note**: The digital output pump on SLAVE units depends on the initial configuration. It is not possible to use the pump if the
system is configured with only one MASTER pump unit.
#
DESCRIPTION COLD AIR TYPE
NO1
COMPRESSOR stage 1/
VENTILATOR
NO2
**PUMP
NO3
SECOND STAGE
NO4
RECOVERY
SET POINTS
When we start configuring the unit for the first time all the preload parameters have a default value, these values are stored in permanent
memory but can be changed depending on the application of the unit.
The values can be changed from the display and the submenus require a password if you want to change the values; if an option is not
included in the display menu the data is only an internal value in the controller and will be visible only if that mode is selected.
The table below has a description of each default set point and can be set to any value in the range column.
iom-clic-cf-eng
DESCRIPTION HOT AIR TYPE
COMPRESSOR stage 1 /
VENTILATOR
PUMP (NOT INCLUDED IN ALL
UNITS)
HEAT VALVE
DESCRIPTION HOT AIR TYPE
INJECTION TEMPERATURE
RETURN TEMPERATURE
SUCTION
CONDENSER TEMPERATURE
DESCRIPTION HOT AIR TYPE
HIGH PRESSURE
LOW PRESSURE
EVAPORATOR FLOW
PHASE MOTOR PROTECTOR
DESCRIPTION HOT AIR TYPE
COMPRESSOR stage 1/
VENTILATOR
**PUMP
SECOND STAGE
RECOVERY
60
Unit Controller Operation
SIGNAL TYPE
EXPECTED RANGE
DRY CONTACT
DRY CONTACT
DRY CONTACT
SIGNAL TYPE
EXPECTED RANGE
NTC
r25=10kΩ + 1%
NTC
r25=10kΩ + 1%
NTC
r25=10kΩ + 1%
NTC
r25=10kΩ + 1%
SIGNAL TYPE
EXPECTED RANGE
DRY CONTACT
DRY CONTACT
DRY CONTACT
DRY CONTACT
SIGNAL TYPE
EXPECTED RANGE
DRY CONTACT
24VAC
DRY CONTACT
24VAC
DRY CONTACT
24VAC
DRY CONTACT
www.clima-flex.com
24VAC
24VAC
N/A
N/A
N/A
N/A
N/A
N/A