Sequence Of Operation

Figure 46. Sequence of operation of the unit.
Unit Power up
Unit in OFF state
Is unit
enabled?
Yes
Is motor
saver alarm
active?
No
Is switch
"Reset"
button
on?
Yes
Evaporator pump
output on
Is flow
present?
1
www.clima-flex.com
No
Yes
No
No
63
1
1
Wait the time for the
start up compressor
The contactor auxiliar
remains on while chiller
is enabled
Is the protection
module or
frecuency
variator of the
compressor
active?
No
Keep pump and auxiliary
output on while the
chiller is enabled
Is there
enough
load to
start
chiller?
Yes
Start the circuit
Operation of circuit in
stabilization
2
Yes
No
iom-clic-cf-eng