Chiller Parameters Configuration
I/O CONFIGURATION
AI
ANALOG INPUTS
1
Tin Evaporator
2
Tout Evaporator
3
Liquid Pressure
4
Suction Temperature
5
Suction Pressure
6
Discharge Pressure
7
Crankcase Temp
8
Main Water Iny Temp
9
Main Water Ret Temp
10
Discharge Temperature
11
Liquid Temperature
12
Air Ambient Temperature
13
Control Panel Temp
14
Drive Panel Temp
DI
DIGITAL INPUTS
1
On/Off
2
3
High Pressure Switch
4
Compressor Status
5
6
Flow Switch Evap
7
Phase Protector Switch
8
Pump/Fan1 Evaporator Overload
9
Detector Gas Sensor
10
Inv Fan 1 Alarm
11
Inv Fan 2 Alarm
12
Oil Level Switch
13
www.clima-flex.com
-50.0
110.0
NTC-10K
-50.0
110.0
NTC-10K
0.0
45.0
0-5 V
-50.0
110.0
NTC-10K
0.0
45.0
0-5 V
0.0
45.0
0-5 V
-50.0
110.0
NTC-10K
-50.0
110.0
NTC-10K
-50.0
110.0
NTC-10K
-50.0
110.0
NTC-10K
-50.0
110.0
NTC-10K
-50.0
110.0
NTC-10K
-50.0
110.0
NTC-10K
-50.0
110.0
NTC-10K
0
1
N.O.
0
1
N.C.
0
1
N.O.
0
1
N.C.
0
1
N.C.
0
1
N.O.
0
1
N.C.
0
1
N.C.
0
1
N.C.
0
1
N.C.
87
Read
18502
Read
18503
Read
18511
Read
18506
Read
18505
Read
18504
Read
18510
Read
18512
Read
18513
Read
18507
Read
18509
°C
Read
18508
Read
18514
Read
18515
Read
17502
Read
17505
Read
17504
Read
17508
Read
17515
Read
17509
Read
17517
Read
17518
Read
17519
Read
17516
iom-clic-cf-eng