Daikin Clima-Flex CLIC Series Installation, Operation And Maintenance Manual page 116

Air-cooled scroll compressor chiller water generator unit, refrigerant hfc-410a or 454b 50/60 hz
Hide thumbs Also See for Clima-Flex CLIC Series:
Table of Contents

Advertisement

Problem
Possible causes
Low oil level.
Insufficient water flow - level too high.
Solenoid valve return oil not open.
Short cycling.
Excess liquid in crankcase - level too high.
Compressor oil
level too high or
Level too high with compressor operation.
too low.
Operation or selection of expansion value.
Compressor mechanical problems.
Incorrect oil for application.
Oil collapse in remote piping.
Loose fitting in oil line
Compressor
Control band not properly adjusted.
staging intervals
too short.
Water temperature sensor failure.
Insufficient water flow.
Rapid temperature or flow changes.
Oversized equipment.
Light loads.
Equipment will
Inadequate voltage.
not run.
Reset switch is off.
No water flow in the system.
Water flow is reversed.
Set temperature value is an incorrect
setting.
Unit runs, but
does not cool
sufficiently.
High condensing temperature.
Equipment does not have sufficient water
flow.
No supply voltage.
The fan does not
work.
Motor defective.
Motor thermal protection switch open.
iom-clic-cf-eng
Troubleshooting Chart
Possible corrective actions
Adjust the water flow required for the equipment.
Check or replace (if necessary) the valve and adjust the proper
superheat.
Check circuit and possible problem of solenoid valve not opening,
if necessary replace.
Check pressure drop or temperature for diagnostics.
Check means of regulating condenser temperature.
If the system has excess oil, recover and adjust by observing the
sight glass on the compressor.
Correct power supply.
Check electrical circuit for possible problem. Then replace
compressor.
Check all connections and tighten, if necessary replace contactors.
See corrective steps for high discharge pressure.
Correct to bring conditions within allowable limits.
Check and correct.
Set correct superheat.
Check for possible problem. Then replace the compressor.
Check and stabilize load or correct control settings for the
application.
Evaluate equipment selection.
Checking and adjusting the load.
Check voltage and correct it.
Power up.
Flush the system.
Check water direction.
Set values.
Check data sheet and check system for leaks.
Check condenser and repair.
Check technical data, check filter in water line and adjust flow if
necessary.
Check electrical circuit (line down).
Contact the manufacturer.
Check operating conditions, if necessary contact the manufacturer.
116