8 Appendix A: Ampacity calculations for IQ8 Commercial
Microinverter system
Enphase IQ8 Commercial Microinverter supports two series connected PV modules and has a four-pin
output configuration (L1, L2, L3, and neutral sense) with Power on two pins and phase sensing on the
other two pins.
IQ8 Commercial Microinverters are connected across the L-L 208 V connection. The single-phase IQ8
Commercial Microinverter achieves the three-phase configuration and phase balancing using the
three-phase QD Cable rotation. The following figure shows the phase rotation of the QD Cable for a
branch circuit of 9 IQ8 Commercial Microinverters. As shown, the QD Cable rotation creates a balanced
three-phase configuration with L1-L2: 3 microinverters, L2-L3: 3 microinverters, and L1-L3: 3
microinverters connected across each phase.
The branch circuit calculations shall involve vector mathematics for current addition as each
microinverter is connected across L-L and shall contribute current to all three lines – L1, L2, and L3
conductors. To simplify the current calculations, refer to the following formulas. We shall use √3
multipliers for converting phase current to line current.

8.1 Branch circuit current calculations

The equation to calculate ampacity for one branch in a 208 V three-phase system is:
Current (amps per branch) = [(Maximum continuous output power of microinverter) × (maximum
number of microinverters per phase L-L) ×√3] ÷ (208 volts)
The equation to determine OCPD sizing for a three-phase system is:
OCPD Sizing = [(Maximum continuous output power of microinverter) × (maximum number of
microinverters per phase L-L)
× √3 ] ÷ (208 volts) × 1.25 (safety factor)
Use these calculations to determine ampacity in three-phase systems, as shown in the following
sections.
NOTE:
Each of the three-line conductors in a balanced three-phase system carries this
current. The neutral sense does not carry any current but is used for microinverter
communications and sensing.
NOTE: In
case of an imbalanced system where each phase has a different number of
microinverters, consider the largest number of microinverters in a phase for OCPD sizing
calculations.
64
to delete the microinverter from the IQ Gateway Commercial 2 database.
Figure 44: QD Cable rotation for IQ8 AC branch circuit
© 2023 Enphase Energy Inc. All rights reserved.
IQ8 Commercial Microinverter grid-tied PV system
November 2023
USG-00026-1.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Iq8p-3p-72-e-usIq8h-3p-72-e-us

Table of Contents