Technical data
32
12.2

Output

12.2.1
Output signal
Description
4 to 20 mA (two-wire)
PMP11: 0 to 10 V output (three-wire)
1)
Product Configurator, order code for "Output"
12.2.2
Signal range 4 to 20 mA
3.8 mA to 20.5 mA
12.2.3
Load (for 4 to 20 mA devices )
In order to guarantee sufficient terminal voltage in two-wire devices, a maximum load
resistance R (including line resistance) must not be exceeded depending on the supply
voltage U
of the supply unit.
B
1
Power supply 10 to 30 V DC for intrinsically safe device versions
2
R
maximum load resistance
Lmax
U
Supply voltage
B
12.2.4
Load resistance (for 0 to 10 V devices)
The load resistance must be ≥ 5 [kΩ].
12.2.5
Signal on alarm 4 to 20 mA
The response of the output to error is regulated in accordance with NAMUR NE43.
Factory setting MAX alarm: >21 mA
Alarm current
Device
Description
PMP21
Adjusted min. alarm current
PMP23
1)
Product Configurator, order code for "Service"
R Lmax
[ ] W
870
435
U
10
20
30
B
[V]
1
U
10V
-
R max
B
2
£
L
23mA
Cerabar PMP11, PMP21, PMP23
1)
Option
1
2
1)
Option
IA
Endress+Hauser
A0029452