PRD1000 Analog Input Process Meter

Setting the Relay Operation (relay)

This menu is used to set up the operation of the relays.
!
Caution!
1.
Relay action
a.
Automatic reset only (non-latching)
b.
Automatic + manual reset at any time (non-latching)
c.
Latching (manual reset only)
d.
Latching with Clear (manual reset only after alarm
condition has cleared)
e.
Pump alternation control (automatic reset only)
f.
Sampling (the relay is activated for a user-specified time)
g.
Off (relay state controlled by Interlock feature)
2.
Set point
3.
Reset point
4.
Fail-safe operation
a.
On (enabled)
b.
Off (disabled)
5.
Time delay
a.
On delay (0-999.9 seconds)
b.
Off delay (0-999.9 seconds)
6.
Relay action for loss (break) of 4-20 mA input (ignore, on, off)
During setup, the relays do not follow the input and
they will remain in the state found prior to entering
the Relay menu.