PRD1000 Analog Input Process Meter
Error Message (Error)
An error message indicates that the calibration or scaling process was
not successful.
After the error message is displayed, the meter reverts to the input prior
to the failure during calibration or scaling and to input 1 during internal
calibration, allowing the appropriate input signal to be applied or
programmed.
The error message might be caused by any of the following conditions:
1.
Input signal is not connected to the proper terminals or it is
connected backwards.
2.
Wrong signal selection in Setup menu.
3.
Minimum input span requirements not maintained.
4.
Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and
input 2 signals required to complete the calibration or scaling of the meter.
Input Range
4-20 mA
10 VDC
Input 1 & Input 2 Span
0.15 mA
0.10 VDC
39