PRD1000 Analog Input Process Meter
Error Message (Error)
An error message indicates that the calibration or scaling process was
not successful.
The error message might be caused by any of the following conditions:
1.
Input signal is not connected to the proper terminals, or it is
connected backwards.
2.
Wrong signal selection in Setup menu.
3.
Minimum input span requirements not maintained.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and
input 2 signals required to complete the calibration or scaling of the meter.
Input Range
4-20 mA
 10 VDC
Input 1 & Input 2 Span
0.15 mA
0.10 VDC
77