Pump Alternation Control Applications (Altern)

For pump control applications where two or more similar pumps are
used to control the level of a tank or a well, it is desirable to have all the
pumps operate alternately. This prevents excessive wear and
overheating of one pump over the lack of use of the other pumps.
Up to 2 relays can be set up to alternate every time an on/off pump
cycle is completed. The set points and reset points can be programmed,
so that the first pump on is the first pump off.
Application #1: Pump Alternation Using Relays 1 & 2
Relays 1 and 2 are set up for pump alternation.
Set and Reset Point Programming
Relay
Set Point
1
30.000
2
35.000
Pump Alternation Operation
1.
Pump #1 turns on when level reaches 30.000, when level drops
below 10.000, pump #1 turns off.
2.
The next time level reaches 30.000, pump #2 turns on, when level
drops below 10.000, pump #2 turns off.
3.
If the level doesn't reach 35.000, pump #1 and pump #2 will be
operating alternately.
4.
If pump #1 cannot keep the level below 35.000, pump #2 will turn
on at 35.000, then as the level drops to10.000, pump #1 turns off,
pump #2 is still running and shuts off below 5.000.
5.
Notice that with the set and reset points of pump #2 outside the
range of pump #1, the first pump on is the first pump to go off.
Reset Point
10.000
5.000
58
Instruction Manual
Function
Controls pump #1
Controls pump #2