PRD1000 Analog Input Process Meter
For use with Bindicator Model TDR-2000
0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
NEMA 4X, IP65 Front
Universal 85-265 VAC, or 12/24 VDC Input Power Models
Large Dual-Line 6-Digit Display, 0.60" & 0.46"
Dual-Scale for some Level Applications – Single Input
Sunlight Readable Display Models
Isolated 24 VDC Transmitter Power Supply
Signal Input Conditioning for Flow & Round Horizontal Tanks
Programmable Display & Function Keys
32-Point, Square Root, or Exponential Linearization
Multi-Pump Alternation Control
2 Relays Option
RS-485 Serial Communication Options
Tare Function
®
Modbus
Custom configuration available from Bindicator
www.bindicator.com
Instruction Manual
RTU Communication Protocol Standard
O
r
d
e
r
O
r
d
e
r
622 Mary Street; Suite 101; Warminster, PA 18974
Phone: 267-673-8117 - Fax: 267-673-8118
C
A
B
C
A
B
f
r
o
m
:
f
r
o
m
:
Sales@cabriggs.com
r
i
g
g
s
C
o
m
r
i
g
g
s
C
o
m
-
www.cabriggs.com
p
a
n
y
p
a
n
y

Advertisement

Table of Contents
loading

Summary of Contents for Bindicator PRD1000

  • Page 1 PRD1000 Analog Input Process Meter Instruction Manual  For use with Bindicator Model TDR-2000  0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs  NEMA 4X, IP65 Front  Universal 85-265 VAC, or 12/24 VDC Input Power Models ...
  • Page 2 Bindicator warrants this product against defects in material or workmanship for the specified period under “Specifications” from the date of shipment from the factory. Bindicator’s liability under this limited warranty shall not exceed the purchase value, repair, or replacement of the defective unit.
  • Page 3: Table Of Contents

    PRD1000 Analog Input Process Meter Instruction Manual Table of Contents INTRODUCTION ------------------------------------------------------------ 7   ORDERING INFORMATION --------------------------------------------- 7   SPECIFICATIONS ---------------------------------------------------------- 8     General ------------------------------------------------------------------------------- 8 Process Input -------------------------------------------------------------------- 10   Relays ------------------------------------------------------------------------------ 11   ®   Modbus RTU Serial Communications ---------------------------------- 12 COMPLIANCE INFORMATION ---------------------------------------------- 13  ...
  • Page 4 PRD1000 Analog Input Process Meter Instruction Manual   Bindicator PRD1000 Display Software ------------------------------ 37 Scaling the Meter (SCALE) ---------------------------------------------- 37   Dual-Scale for Level Application -------------------------------------- 38     Calibrating the Meter with External Source (Cal) ----------------- 40 Setting the Display Parameter & Intensity (dsplay) ----------------- 41  ...
  • Page 5 PRD1000 Analog Input Process Meter Instruction Manual   Noise Filter Bypass (bypass) ---------------------------------------------- 67 Rounding Feature (round) ------------------------------------------------- 67   Modbus RTU Serial Communications (serial) ---------------------- 68     Select Menu (SElect) ------------------------------------------------------- 69 Signal Input Conditioning (Functn) -------------------------------------- 69  ...
  • Page 6 Figure 5. Jumper Configuration for 12/24 VDC Power ....18   Figure 6. Transmitter Supply Voltage Selection ......19     Figure 7. Connector Labeling for Fully Loaded PRD1000 ....20 Figure 8. Power Connections ............20   Figure 9. Transmitters Powered by Internal Supply ......21  ...
  • Page 7: Introduction

    Instruction Manual INTRODUCTION The PRD1000 is a multi-purpose, easy to use digital process meter ideal for level, flow rate, temperature, or pressure transmitter applications. It accepts current and voltage signals (e.g. 4-20 mA, 0-10 V). Three of the front panel buttons can be custom- programmed for a specific operation.
  • Page 8: Specifications

    PV1, PV2, PCT, d r-u, d gross, d nt-g, max/min, max & ASSIGNMENT min, set points, units (small display only), or Modbus input. PROGRAMMING Four front panel buttons, digital inputs, PC and Bindicator METHODS PRD1000 Display software, Modbus registers, or cloning using Copy function.
  • Page 9 PRD1000 Analog Input Process Meter Instruction Manual FUSE Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse NORMAL MODE Greater than 60 dB at 50/60 Hz REJECTION ISOLATION 4 kV input/output-to-power line...
  • Page 10: Process Input

    PRD1000 Analog Input Process Meter Instruction Manual Process Input INPUTS Field selectable: 0-20, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave) ACCURACY ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span TEMPERATURE 0.005% of calibrated span/C max from 0 to 65C ambient,...
  • Page 11: Relays

    PRD1000 Analog Input Process Meter Instruction Manual Relays RATING 2 SPDT (Form C) internal; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads NOISE Noise suppression is recommended for each relay contact SUPPRESSION switching inductive loads;...
  • Page 12: Modbus ® Rtu Serial Communications

    8 bit (1 start bit, 1 or 2 stop bits) PARITY Even, Odd, or None with 1 or 2 stop bits BYTE-TO-BYTE 0.01 – 2.54 second TIMEOUT TURN AROUND Less than 2 ms (fixed) DELAY Note: Refer to the Modbus Register Tables located at www.bindicator.com for details.
  • Page 13: Compliance Information

    PRD1000 Analog Input Process Meter Instruction Manual COMPLIANCE INFORMATION Safety UL & c-UL LISTED USA & Canada UL 508 Industrial Control Equipment UL FILE NUMBER E160849 FRONT PANEL UL Type 4X, NEMA 4X, IP65; panel gasket provided LOW VOLTAGE EN 61010-1:2001...
  • Page 14: Safety Information

    PRD1000 Analog Input Process Meter Instruction Manual Note: Testing was conducted on PRD1000 meters installed through the covers of grounded metal enclosures with cable shields grounded at the point of entry representing installations designed to optimize EMC performance. Declaration of Conformity available at www.bindicator.com...
  • Page 15: Installation

    PRD1000 Analog Input Process Meter Instruction Manual INSTALLATION There is no need to remove the meter from its case to complete the installation, wiring, and setup of the meter for most applications. Instructions are provided for setting up a 12/24 VDC powered meter to operate from 12 VDC and for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see page 18.
  • Page 16: Figure 2. Panel Mounting Details

    PRD1000 Analog Input Process Meter Instruction Manual Gasket Removable Connectors Panel Mounting Mounting Bracket Screw Figure 2. Panel Mounting Details...
  • Page 17: Mounting Dimensions

    PRD1000 Analog Input Process Meter Instruction Manual Mounting Dimensions Figure 3. Meter Dimensions - Side View Figure 4. Meter Dimensions - Top View...
  • Page 18: Configuration For 12 Or 24 Vdc Power Option

    PRD1000 Analog Input Process Meter Instruction Manual Configuration for 12 or 24 VDC Power Option Do not exceed voltage rating of the selected configuration. Warning! Meters equipped with the 12/24 VDC power option are shipped from the factory ready to operate from 24 VDC.
  • Page 19: Connections

    PRD1000 Analog Input Process Meter Instruction Manual Transmitter Supply Voltage Selection (P+, P-) All meters, including models equipped with the 12/24 VDC power option, are shipped from the factory configured to provide 24 VDC power for the transmitter or sensor.
  • Page 20: Connectors Labeling

    M-LINK connector. Otherwise damage will occur to the equipment and the meter. Warning! Figure 7. Connector Labeling for Fully Loaded PRD1000 Power Connections Power connections are made to a two-terminal connector labeled POWER on Figure 7 on page 20. The meter will operate regardless of DC polarity connection.
  • Page 21: Signal Connections

    PRD1000 Analog Input Process Meter Instruction Manual Signal Connections Signal connections are made to a six-terminal connector labeled SIGNAL on Figure 7. The COM (common) terminal is the return for the 4-20 mA and the 10 V input signals. Current and Voltage Connections The following figures show examples of current and voltage connections.
  • Page 22: Modbus Rtu Serial Communications

    The meter is capable of accepting any voltage from -10 VDC to +10 VDC. Modbus RTU Serial Communications Serial communications connection is made to an RJ45 connector labeled M-LINK on Figure 7. For interfacing to the PRD1000, use a RS-485 serial adapter. Relay Connections Relay connections are made to two six-terminal connectors labeled RELAY1 –...
  • Page 23: Switching Inductive Loads

    PRD1000 Analog Input Process Meter Instruction Manual Switching Inductive Loads The use of suppressors (snubbers) is strongly recommended when switching inductive loads to prevent disrupting the microprocessor’s operation. The suppressors also prolong the life of the relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased as complete assemblies.
  • Page 24: F4 Digital Input Connections

    PRD1000 Analog Input Process Meter Instruction Manual F4 Digital Input Connections A digital input, F4, is standard on the meter. This digital input is connected with a normally open contact across F4 and COM, or with an active low signal applied to F4.
  • Page 25: Setup And Programming

    PRD1000 Analog Input Process Meter Instruction Manual SETUP AND PROGRAMMING The meter is factory calibrated prior to shipment to read in milliamps and volts depending on the input selection. The calibration equipment is certified to NIST standards. Overview There are no jumpers to set for the meter input selection.
  • Page 26: Front Panel Buttons And Status Led Indicators

    PRD1000 Analog Input Process Meter Instruction Manual Front Panel Buttons and Status LED Indicators Button Description Status Symbol Menu Alarm 1-2 indicator Flashing: Relay in Right arrow/F1 manual control mode Up arrow/F2 Flashing: Tare Flashing: Relay Enter/F3 interlock switch open...
  • Page 27: Display Functions & Messages

    PRD1000 Analog Input Process Meter Instruction Manual Display Functions & Messages The meter displays various functions and messages during setup, programming, and operation. The following table shows the main menu functions and messages in the order they appear in the menu.
  • Page 28 PRD1000 Analog Input Process Meter Instruction Manual Set display intensity level from 1 to 8 Display d-Inty intensity Relay Enter the Relay menu RELaY Relay 1 setup RLY 1 Relay 1 Action 1 Set relay 1 action Act 1 Automatic...
  • Page 29 PRD1000 Analog Input Process Meter Instruction Manual Set relay condition if loop break detected Loop break break Ignore Ignore loop break condition ignore (Processed as a low signal condition) Relay goes to alarm condition when loop break is detected Relay goes to non-alarm condition when...
  • Page 30: Main Menu

    PRD1000 Analog Input Process Meter Instruction Manual Main Menu The main menu consists of the most commonly used functions: Setup, Reset, Control, and Password.  Press Menu button to enter Programming Mode then press the Up arrow button to scroll main menu.
  • Page 31: Setting Numeric Values

    PRD1000 Analog Input Process Meter Instruction Manual Setting Numeric Values The numeric values are set using the Right and Up arrow buttons. Press Right arrow to select next digit and Up arrow to increment digit value. The digit being changed is displayed brighter than the rest.
  • Page 32: Setting Up The Meter (Setup)

    PRD1000 Analog Input Process Meter Instruction Manual Setting Up the Meter (setup) The Setup menu is used to select: Input signal the meter will accept Dual-scale feature for some level applications Select the display units/tags Decimal point position Programming Menu...
  • Page 33: Setting The Input Signal (Input)

    PRD1000 Analog Input Process Meter Instruction Manual Setting the Input Signal (Input) Enter the Input menu to set up the meter to display current (mA) or voltage (volt) inputs. The current input is capable of accepting any signal from 0 to 20 mA.
  • Page 34: Setting The Input Units Or Custom Tags (Units)

    Display Character Display Character Degree(<) Space Notes: Degree symbol represented by (<) if programming with Bindicator PRD1000 Display software. The letters “m” and “w” use two 7-segment LEDs each; when selected the characters to the right are shifted one position.
  • Page 35: Setting The Decimal Point (Dec Pt)

    PRD1000 Analog Input Process Meter Instruction Manual Press and hold up arrow to auto-scroll the characters in the display. Setting the Decimal Point (dEc pt) The decimal point may be set with up to five decimal places or with no decimal point at all.
  • Page 36: Programming The Meter (Prog)

    Use the Calibrate menu to apply a signal from a calibrator or a flowmeter.  The PRD1000 is a single input meter with dual-scale capability. The Program menu contains the Scale and the Calibrate menus. Note: The Scale and Calibrate functions are exclusive of each other.
  • Page 37: Multi-Point Calibration & Scaling

    The meter can also be programmed using the PC-based Bindicator PRD1000 Display software available for free download at www.bindicator.com. Data logging for one meter at a time is available with Bindicator PRD1000 Display software. More advanced data acquisition may be accomplished by using any Modbus RTU compliant software.
  • Page 38: Dual-Scale For Level Application

    PRD1000 Analog Input Process Meter Instruction Manual Dual-Scale for Level Application The analog input can be displayed in two different scales, by enabling the dual-scale feature (d-SCAL) in the Setup-Input menu, see page 32. To enable the dual-scale feature for some level applications you must select d-SCAL in the Input selection menu.
  • Page 39 PRD1000 Analog Input Process Meter Instruction Manual Error Message (Error) An error message indicates that the calibration or scaling process was not successful. After the error message is displayed, the meter reverts to the input prior to the failure during calibration or scaling and to input 1 during internal calibration, allowing the appropriate input signal to be applied or programmed.
  • Page 40: Calibrating The Meter With External Source (Cal)

    PRD1000 Analog Input Process Meter Instruction Manual Calibrating the Meter with External Source (Cal) Note: To scale the meter without a signal source refer to Scaling the Meter (SCALE), page 37. The meter can be calibrated to display the process variable in engineering units by applying the appropriate input signal and following the calibration procedure.
  • Page 41: Setting The Display Parameter & Intensity (Dsplay)

    PRD1000 Analog Input Process Meter Instruction Manual Setting the Display Parameter & Intensity (dsplay) The main display (Big) can be programmed to display: Process value 1 (PV1) Process value 2 (PV2) Percent of PV1 (PCT) Relay set points Max & min values...
  • Page 42: Display Setup Menu

    PRD1000 Analog Input Process Meter Instruction Manual Display Setup Menu After setting up the input and display, press the Menu button to exit programming and skip the rest of the setup menu. Press the Menu button again and the Up arrow to reach the Program menu and...
  • Page 43: Setting The Relay Operation (Relay)

    PRD1000 Analog Input Process Meter Instruction Manual Setting the Relay Operation (relay) This menu is used to set up the operation of the relays. During setup, the relays do not follow the input and they will remain in the state found prior to entering the Relay menu.
  • Page 44: Setting The Relay Action

    PRD1000 Analog Input Process Meter Instruction Manual Setting the Relay Action Operation of the relays is programmed in the Action menu. The relays may be set up for any of the following modes of operation: Automatic reset (non-latching) Automatic + manual reset at any time (non-latching)
  • Page 45: Programming Set And Reset Points

    PRD1000 Analog Input Process Meter Instruction Manual Programming Set and Reset Points High alarm indication: program set point above reset point. Low alarm indication: program set point below reset point. The deadband is determined by the difference between set and reset points.
  • Page 46: Relay And Alarm Operation Diagrams

    PRD1000 Analog Input Process Meter Instruction Manual Relay and Alarm Operation Diagrams The following graphs illustrate the operation of the relays, status LEDs, and ACK button. High Alarm Operation (Set > Reset) For Manual reset mode, ACK can be pressed anytime to turn "off" relay.
  • Page 47: Low Alarm Operation (Set < Reset)

    PRD1000 Analog Input Process Meter Instruction Manual Low Alarm Operation (Set < Reset) Input Reset de-energized energized Relay Automatic (non-latching) Relay pressed Automatic or Manual (non-latching) Relay pressed Manual (latching) Relay pressed Manual only after passing above Reset (latching with clear) For Manual reset mode, ACK can be pressed anytime to turn "off"...
  • Page 48: High Alarm With Fail-Safe Operation (Set > Reset)

    PRD1000 Analog Input Process Meter Instruction Manual High Alarm with Fail-Safe Operation (Set > Reset) Input de-energized energized Relay Automatic (non-latching) Relay pressed Automatic or Manual (non-latching) Relay pressed Manual (latching) Relay pressed Manual only after passing below Reset (latching with clear) Note: Relay coil is energized in non-alarm condition.
  • Page 49: Low Alarm With Fail-Safe Operation (Set < Reset)

    PRD1000 Analog Input Process Meter Instruction Manual Low Alarm with Fail-Safe Operation (Set < Reset) Input Reset de-energized energized Relay Automatic (non-latching) Relay pressed Automatic or Manual (non-latching) Relay pressed Manual (latching) Relay pressed Manual only after passing above Reset (latching with clear) Note: Relay coil is energized in non-alarm condition.
  • Page 50: Pump Alternation Control Operation

    PRD1000 Analog Input Process Meter Instruction Manual...
  • Page 51: Relay Sampling Operation

    PRD1000 Analog Input Process Meter Instruction Manual Relay Sampling Operation Input Reset Sample Sample Sample Time Time Time Relay When the signal crosses the set point, the relay trips and the sample time starts. After the sample time has elapsed, the relay resets. The cycle repeats every time the set point is crossed, going up for high alarms and going down for low alarms.
  • Page 52: Signal Loss Or Loop Break Relay Operation

    PRD1000 Analog Input Process Meter Instruction Manual Signal Loss or Loop Break Relay Operation The following graph shows the loop break relay operation for a high alarm relay. Input Reset de-energized energized Relay Loop Break = Ignore Relay Loop Break = Off...
  • Page 53: Time Delay Operation

    PRD1000 Analog Input Process Meter Instruction Manual Time Delay Operation The following graphs show the operation of the time delay function. When the signal crosses the set point, the On time delay timer starts and the relay trips when the time delay has elapsed. If the signal drops below the set point (high alarm) before the time delay has elapsed, the On time delay timer resets and the relay does not change state.
  • Page 54: Relay Operation Details

    PRD1000 Analog Input Process Meter Instruction Manual Relay Operation Details Overview The relay capabilities of the meter expand its usefulness beyond simple indication to provide users with alarm and control functions. These capabilities include front panel alarm status LEDs as well as either 2 internal relays.
  • Page 55: Front Panel Leds

    PRD1000 Analog Input Process Meter Instruction Manual Front Panel LEDs The LEDs on the front panel provide status indication for the following: Status Status Alarm 1 Alarm 5 Alarm 2 Alarm 6 Alarm 3 Alarm 7 Alarm 4 Alarm 8 The meter is supplied with four alarm points that include front panel LEDs to indicate alarm conditions.
  • Page 56: Non-Latching Relay (Auto)

    PRD1000 Analog Input Process Meter Instruction Manual Non-Latching Relay (Auto) Automatic reset only Condition Relay Normal Alarm Ack (No effect) Normal In this application, the meter is set up for automatic reset (non-latching relay). Acknowledging the alarm while it is still present has no effect on either the LED or the relay.
  • Page 57: Latching Relay (Lt-Clr)

    PRD1000 Analog Input Process Meter Instruction Manual Latching Relay (Lt-Clr) Manual reset only after alarm condition has cleared Condition Relay Normal Alarm Ack (No effect) Normal In this application, the meter is set up for manual reset only after the signal passes the reset point (alarm condition has cleared).
  • Page 58: Pump Alternation Control Applications (Altern)

    PRD1000 Analog Input Process Meter Instruction Manual Pump Alternation Control Applications (Altern) For pump control applications where two or more similar pumps are used to control the level of a tank or a well, it is desirable to have all the pumps operate alternately.
  • Page 59 PRD1000 Analog Input Process Meter Instruction Manual Setting Up the Interlock Relay (Force On) Feature Relays 1-2 can be set up as interlock relays. To set up the relays for the interlock feature: 1. Access the Setup – Relay – Action menu and set the action to off.
  • Page 60: Reset Menu (Reset)

    PRD1000 Analog Input Process Meter Instruction Manual Reset Menu (reset) The Reset menu is used to reset the maximum or minimum reading (peak or valley) reached by the process; both may be reset at the same time by selecting “reset high & low” ( rst HL ). The tare value used to zero the display may be reset by selecting “reset tare”...
  • Page 61: Setting Up The Password (Pass)

    PRD1000 Analog Input Process Meter Instruction Manual Setting Up the Password (pass) The Password menu is used for programming three levels of security to prevent unauthorized changes to the programmed parameter settings. Pass 1: Allows use of function keys and digital inputs...
  • Page 62: Making Changes To A Password Protected Meter

    PRD1000 Analog Input Process Meter Instruction Manual Making Changes to a Password Protected Meter If the meter is password protected, the meter will display the message Locd ( Locked ) when the Menu button is pressed. Press the Enter button while the message is being displayed and enter the correct password to gain access to the menu.
  • Page 63: Advanced Features Menu

    PRD1000 Analog Input Process Meter Instruction Manual Advanced Features Menu To simplify the setup process, functions not needed for most applications are located in the Advanced Features menu. Press and hold the Menu button for three seconds to access the...
  • Page 64: Advanced Features Menu & Display Messages

    PRD1000 Analog Input Process Meter Instruction Manual Advanced Features Menu & Display Messages The following table shows the functions and messages of the Advanced Features menu in the order they appear in the menu. Display Parameter Action/Setting Filter Set noise filter value...
  • Page 65 PRD1000 Analog Input Process Meter Instruction Manual Display Parameter Action/Setting break Break Set input break condition operation Maximum Program maximum mA output allowed Minimum Program minimum mA output allowed 4 mA output Enter mA output value read by milliamp 4 mA meter with at least 0.001 mA resolution...
  • Page 66 PRD1000 Analog Input Process Meter Instruction Manual Copy Enter copy function Copy Send Send meter settings to another meter send Done Copy function completed done Diagnostics Display parameter settings Diag Input selection Input Input Select the display units/tags units Units...
  • Page 67: Noise Filter (Filter)

    PRD1000 Analog Input Process Meter Instruction Manual Noise Filter (filter) The noise filter is available for unusually noisy signals that cause an unstable process variable display. The noise filter averages the input signal over a certain period. The filter level determines the length of time over which the signal is averaged.
  • Page 68: Modbus Rtu Serial Communications (Serial)

    RS-485 adapter option is required; see Ordering Information on page 7 for details. Do not connect any equipment other than Bindicator’s cables, or meters to the RJ45 M-LINK connector. Otherwise damage will occur to the Warning! equipment and the meter.
  • Page 69: Select Menu (Select)

    PRD1000 Analog Input Process Meter Instruction Manual Select Menu (SElect) The Select menu is used to select the signal input conditioner applied to the input (linear, square root, programmable exponent, or round horizontal tank), and low-flow cutoff. The multi-point linearization is part of the linear function selection.
  • Page 70 PRD1000 Analog Input Process Meter Instruction Manual Square Root Linearization (Square) The square root function can be used to linearize the signal from a differential pressure transmitter and display flow rate in engineering units. Programmable Exponent Linearization (Prog E) The programmable exponent can be used to linearize the signal from level transmitters in open-channel flow applications using weirs and flumes.
  • Page 71 PRD1000 Analog Input Process Meter Instruction Manual Round Horizontal Tank Linearization (rHt) This function automatically calculates the volume in a round horizontal tank with flat ends. Set the display for the desired decimal point and engineering units before entering the round horizontal tank function. Select units, inches or cm for the tank dimensions.
  • Page 72: Low-Flow Cutoff (Cutoff)

    PRD1000 Analog Input Process Meter Instruction Manual Low-Flow Cutoff (CutofF) The low-flow cutoff feature allows the meter to be programmed so that the often-unsteady output from a differential pressure transmitter, at low flow rates, always displays zero on the meter.
  • Page 73: Programmable Function Keys User Menu (User)

    PRD1000 Analog Input Process Meter Instruction Manual Programmable Function Keys User Menu (user) The User menu allows the user to assign the front panel function keys F1, F2, and F3, and the digital input F4 to access most of the menus or to activate functions immediately (e.g.
  • Page 74: Tare (Tare)

    PRD1000 Analog Input Process Meter Instruction Manual Tare (tare) The tare function zero’s out the display. In the case of scale weight, tare is used to eliminate container weight and provide net weight readings. There are two tare functions; Capture Tare and Reset Tare.
  • Page 75: Internal Source Calibration (Ical)

    PRD1000 Analog Input Process Meter Instruction Manual Internal Source Calibration (ICAL) The meter is factory calibrated prior to shipment to read in milliamps and volts depending on the input selection. The calibration equipment is certified to NIST standards. The use of calibrated signal sources is necessary to calibrate the internal source of the meter.
  • Page 76 PRD1000 Analog Input Process Meter Instruction Manual The display moves to the high input calibration ( C Hi ). Apply the high input signal and press Enter. Set the display for the high input calibration, in the same way as it was set for the low input calibration, typically 20.000 mA.
  • Page 77 PRD1000 Analog Input Process Meter Instruction Manual Error Message (Error) An error message indicates that the calibration or scaling process was not successful. The error message might be caused by any of the following conditions: Input signal is not connected to the proper terminals, or it is connected backwards.
  • Page 78: Meter Operation

    PRD1000 Analog Input Process Meter Instruction Manual METER OPERATION The meter is capable of accepting current (0-20 mA, 4-20 mA) and voltage signals (0-5 V, 1-5 V, 0-10 V,  10 V) and displaying these signals in engineering units from -99999 to 999999 (e.g. a 4-20 mA signal could be displayed as -50.000 to 50.000).
  • Page 79: F4 Operation

    PRD1000 Analog Input Process Meter Instruction Manual F4 Operation A digital input, F4, is standard on the meter. This digital input is programmed identically to function keys F1, F2, and F3. The input is triggered with a contact closure to COM, or with an active low signal.
  • Page 80: Troubleshooting

    PRD1000 Analog Input Process Meter Instruction Manual TROUBLESHOOTING The rugged design and the user-friendly interface of the meter should make it unusual for the installer or operator to refer to this section of the manual. However, due to the many features and functions of the meter, it’s possible that the setup of the meter does not agree with what an...
  • Page 81: Reset Meter To Factory Defaults

    PRD1000 Analog Input Process Meter Instruction Manual Reset Meter to Factory Defaults When the parameters have been changed in a way that is difficult to determine what’s happening, it might be better to start the setup process from the factory defaults.
  • Page 82: Factory Defaults & User Settings

    PRD1000 Analog Input Process Meter Instruction Manual Factory Defaults & User Settings The following table shows the factory setting for most of the programmable parameters on the meter. Next to the factory setting, the user may record the new setting for the particular application.
  • Page 83 PRD1000 Analog Input Process Meter Instruction Manual Parameter Display Default Setting User Setting Relay 3 reset point 2.500 RSt 3 Relay 4 action Automatic Act 4 Relay 4 set point 4.000 Set 4 Relay 4 reset point 3.500 RSt 4...
  • Page 84 PRD1000 Analog Input Process Meter Instruction Manual Parameter Display Default Setting User Setting Digital input 1 Menu dI 1 Digital input 2 Right arrow dI 2 Digital input 3 Up arrow dI 3 Digital input 4 Enter dI 4 Digital output 1...
  • Page 85: Troubleshooting Tips

    PRD1000 Analog Input Process Meter Instruction Manual Troubleshooting Tips Symptom Check/Action No display at all Check power at power connector Not able to change setup or Meter is password-protected, enter programming, Locd is displayed correct six-digit password to unlock Check:...
  • Page 86: Alphabetical List Of Display Functions & Messages

    PRD1000 Analog Input Process Meter Instruction Manual Alphabetical List of Display Functions & Messages Display Parameter Action/Setting Description Flashing Overrange condition 999999 -99999 display Underrange condition Acknowledge Acknowledge relays Set relay 1 action Act 1 Action 1 Assign digital output to Alarm 1-8...
  • Page 87 PRD1000 Analog Input Process Meter Instruction Manual Display Parameter Action/Setting Description Cutoff Set low-flow cutoff CutofF Display gross Select to display the gross D Gros Select to display the net/gross D nt-G Display net/gross Select to display the max D Hi Display high Display H&L...
  • Page 88 PRD1000 Analog Input Process Meter Instruction Manual Display Parameter Action/Setting Description Done Copy function completed done Dual-scale Enter d-SCAL menu and select Yes for dual- d-SCAL scale display or No for single scale display Select to display set point 1 (1-8)
  • Page 89 PRD1000 Analog Input Process Meter Instruction Manual Display Parameter Action/Setting Description LED test Test all LEDs LED t Length Enter the tank’s length in inches Length Set meter for linear function and select Linear Linear number of linearization points Assign digital input to display max on the...
  • Page 90 PRD1000 Analog Input Process Meter Instruction Manual Display Parameter Action/Setting Description Output 1 Program output 1 value (e.g. 4.000 mA) Out 1 Output 2 Program output 2 value (e.g. 20.000 mA) Out 2 Enter the Password menu pass Password Set or enter Password 1...
  • Page 91 PRD1000 Analog Input Process Meter Instruction Manual Display Parameter Action/Setting Description Sampling Set relay for sampling operation Sampl Scale 1 Enter the Scale 1 menu for PV1 SCAL 1 Enter the Scale 2 menu for PV2 SCAL 2 Scale 2...
  • Page 92 150 Venture Blvd Spartanburg SC 29306 Tel.: (800)778-9242 • Fax: (864)574-8063 Email: sales@bindicator.com www.bindicator.com PRD180213 Rev A LIM6000VM_A SFT039 Ver 3.100 & up 02/13...

Table of Contents