Troubleshooting; Diagnosing A Problem - Vent-Axia Sentinel Kinetic Operation Manual

Mechanical ventilation/heat recovery (mvhr)
Hide thumbs Also See for Sentinel Kinetic:
Table of Contents

Advertisement

Troubleshooting

Troubleshooting

Diagnosing a Problem

In the event of a problem, always troubleshoot the unit according to:
Fault code displayed on the Control Unit or Remote Wired Control.
Fault LED if connected.
If no indications are displayed, then troubleshoot problem according to the fault symptom as described in the
following tables.
Service/Fault Code Screens
The Service screen is displayed, alternating with the
Fault Code screen, when a fault has caused the unit to
switch off and you must phone the telephone number
displayed on the screen for assistance.
The Fault Code screen is displayed, alternating with
the Service screen, when a fault has occurred. Take
note of the fault code when reporting a fault.
For assistance contact the service provider and quote the fault code number. The following fault codes numbers
may be displayed. Code numbers are added together if more than one is detected.
Table 2: Fault Codes
Code
01
02
04
08
16
32
Sentinel Kinetic MVHR Operation & Monitoring
Problem
Supply Fan not running
Extract Fan not running
Control PCB 24 V fuse (FS1) failure
Temperature sensor T1 (supply) faulty
Temperature sensor T2 (extract) faulty
Wired Remote Control failure
Service Phone
01293nnnnnn
Fault Code
01
17