Operation and Monitoring
Boost & Purge Screens
Boost Screen
Pressing the
when extra ventilation is required.
No. of presses
N.B Additional airflow modes are available from the
button when Control Mode 02 is selected in the
start-up screens see Appendix One for further
details.
If the wireless boost option is fitted, this can be
triggered from the wireless transmitter/boost switch.
If the installation has switch sensors, is wired to the
lighting, has Vent-Wise sensors or if the internal time
switch is set for periodic operation, operation will
change from normal to boost automatically. Pressing
the
button will reveal a code to show which device
has activated boost.
s1 = Switch S/W1
s2 = Switch S/W2
s3 = Switch S/W3
s4 = Switch SW4
s5 = Switch SW5
v1 = Vent-Wise Input S/W1
v2 = Vent-Wise Input S/W2
v3 = Vent-Wise Input S/W3
ls = Switched live (LS)
w1-4 = Wireless controller
c1-3 = Internal Time switch
If running on boost due to pressing the
device will 'take over' the boost. Flow will return to low /
normal when that device switches off. If a number of
different devices are calling for boost flow, the unit will
run at boost until the last one has reverted to normal.
Sentinel Kinetic MVHR Operation & Monitoring
button activates boost airflow mode
Boost action
(Control Mode 01)
1
Boosts for 30 minutes
2
Boosts for 60 minutes
3
Boosts continuously
4
Back to Normal flow rate
Boost Airflow
50 %
button, a
11