2.2 WinCon Utility

The WinCon Utility provides many tools to save/view the system information
registry and to setup the HTTP/FTP path and update non-volatile internal memory
within the Wincon-8000 embedded controller. This handy utility (WinCon Utility 1.exe
located in the Compact Flash/icpdas/Tools directory) should be located in the
computer's Program group. Therefore, you can launch it on the computer through
Start
Programs
functions within the following five tabs:
Save Registry Tab
System Config Tab
Auto-execute Tab
Version Update Tab
Com Tab
About WinCon Utility 1 Tab
Save Registry Tab
This tab provides functions to save/view the registry of the systems information
and to setup the HTTP/FTP directory path. It is very important to save the registry
when you change any system information. Then you need to click the "Save
and Reboot" button to renew the system configuration. If you do not save the
current configuration into the registry, you will lose your information settings
when you reboot the Wincon-8000.
Note: The OS image in flash memory will crash if we push the reset or
power-off buttons for WinCon-8000 whilst it was writing the registry
settings to flash memory. It will take 10-15 seconds to save the
registry settings. Add these notes to your user manual because it is
very important!
WinCon Utility menu. The WinCon Utility provides many