Samsung NASA with KNX, Serial and IP support
ERROR CODE
219
Error on temperature sensor located on MCU intercooler inlet (Short or Open)
220
Error on temperature sensor located on MCU intercooler outlet (Short or Open)
221
Error on outdoor temperature sensor of outdoor unit (Short or open)
231
Error on COND OUT temperature sensor of main outdoor unit (Short or Open)
241
COND OUT sensor is detached
251
Error on discharge temperature sensor of compressor 1 (Short or Open)
257
Error on discharge temperature sensor of compressor 2 (Short or Open)
262
Discharge temperature sensor of compressor 1 is detached from the sensor holder on the pipe
263
Discharge temperature sensor of compressor 2 is detached from the sensor holder on the pipe
266
Top sensor of compressor 1 is detached
267
Top sensor of compressor 2 is detached
269
Suction temperature sensor is detached from the sensor holder on the pipe
276
Error on top sensor of compressor 1 (Short or Open)
277
Error on top sensor of compressor 2 (Short or Open)
291
Refrigerant leakage or error on high pressure sensor (Short or Open)
296
Refrigerant leakage or error on low pressure sensor (Short or Open)
308
Error on suction temperature sensor (Short or Open)
311
Error on temperature sensor of double layer pipe/liquid pipe (sub heat exchanger) (Short or Open)
321
Error on EVI (ESC) IN temperature sensor (Short or Open)
322
Error on EVI (ESC) OUT temperature sensor (Short or Open)
323
Error on suction sensor 2 (Short or Open)
346
Error due to operation failure of Fan2
347
Motor wire of Fan2 is not connected
348
Lock error on Fan2 of outdoor unit
353
Error due to overheated motor of outdoor unit's Fan2
355
Error due to overheated IPM of Fan2
361
Error due to operation failure of inverter compressor 2
364
Error due to over-current of inverter compressor 2
365
V-limit error of inverter compressor 2
366
Error due to over voltage /low voltage of inverter PBA2
367
Error due to unconnected wire of compressor 2
368
Output current sensor error of inverter PBA2
369
DC voltage sensor error of inverter PBA2
374
Heat sink temperature sensor error of inverter PBA2
378
Error due to overcurrent of Fan2
385
Error due to input current of inverter 2
386
Over-voltage/low-voltage error of Fan2
387
Hall IC connection error of Fan2
389
V-limit error on Fan2 of compressor
393
Output current sensor error of Fan2
396
DC voltage sensor error of Fan2
399
Heat sink temperature sensor error of Fan2
400
Error due to overheat caused by contact failure on IPM of Inverter PBA2
407
Compressor operation stop due to high pressure protection control
410
Compressor operation stop due to low pressure protection control or refrigerant leakage
416
Compressor operation stop due to discharge temperature protection control
425
Phase reversal or phase failure (3Ø outdoor unit wiring, R-S-T-N ), connection error on 3 phase input
428
Compressor operation stop due abnormal compression ratio
438
EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect connector insertion of EVI (ESC) EEV
Page 42 of 44
DESCRIPTION
Error Codes