Integration into KNX Systems
Object name
Operating Mode (all units)
Fan Speed (all units)
Fan Speed AUTO (all units)
Vane position swing (all units)
Temperature Setpoint (all units)
Vent. On/Off (all units)
Hot Water On/Off (all units)
Table 7. Individual units signals
Object name
Control_On/Off
Status_OXXUXX_On/Off
Control_OXXUXX_Operation mode
Status_OXXUXX_Operation mode
Control_OXXUXX_Operation mode
USER MANUAL Version 1.0.6
Possible values
0: Cool
1: Heat
2: Dry
3: Fan
4: Auto
5: Cool Storage
6: Heat Storage
1: Low
2: Mid
3: High
1: Set auto fan
0: Stop auto fan
0: Swing Off
1: Swing On
Cool: 18 .. 30°C / 64 .. 86°F
Heat: 16 .. 30°C / 61 .. 86°F
0: Off
1: On
0: Off
1: On
Possible values
0: Off
1: On
0: Off
1: On
0: Auto
1: Heat
3: Cool
9: Fan
14: Dry
0: Auto
1: Heat
3: Cool
9: Fan
14: Dry
0: Auto
1: Heat
2: Dry
3: Fan
4: Cool
5: Cool Storage
6: Heat Storage
Samsung NASA with KNX, Serial and IP support
DPT
5.x (1byte)
5.x (1byte)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
9.001-DPT_Value_Temp (2byte)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
DPT
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
20.105-DPT_HVACContrMode
(1byte)
20.105-DPT_HVACContrMode
(1byte)
5.x (1byte)
Flags
W
W
W
W
W
W
W
Flags
W
R, T
W
R, T
W
Page 27 of 44