HMS Networks Intesis IN770AIR00 O000 Series User Manual page 30

Samsung nasa with knx, serial and ip support
Hide thumbs Also See for Intesis IN770AIR00 O000 Series:
Table of Contents

Advertisement

Integration into KNX Systems
Object name
Operating Mode (all units)
Fan Speed (all units)
Fan Speed AUTO (all units)
Vane position swing (all units)
Temperature Setpoint (all units)
Vent. On/Off (all units)
Hot Water On/Off (all units)
Table 7. Individual units signals
Object name
Control_On/Off
Status_OXXUXX_On/Off
Control_OXXUXX_Operation mode
Status_OXXUXX_Operation mode
Control_OXXUXX_Operation mode
USER MANUAL Version 1.0.6
Possible values
0: Cool
1: Heat
2: Dry
3: Fan
4: Auto
5: Cool Storage
6: Heat Storage
1: Low
2: Mid
3: High
1: Set auto fan
0: Stop auto fan
0: Swing Off
1: Swing On
Cool: 18 .. 30°C / 64 .. 86°F
Heat: 16 .. 30°C / 61 .. 86°F
0: Off
1: On
0: Off
1: On
Possible values
0: Off
1: On
0: Off
1: On
0: Auto
1: Heat
3: Cool
9: Fan
14: Dry
0: Auto
1: Heat
3: Cool
9: Fan
14: Dry
0: Auto
1: Heat
2: Dry
3: Fan
4: Cool
5: Cool Storage
6: Heat Storage
Samsung NASA with KNX, Serial and IP support
DPT
5.x (1byte)
5.x (1byte)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
9.001-DPT_Value_Temp (2byte)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
DPT
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
20.105-DPT_HVACContrMode
(1byte)
20.105-DPT_HVACContrMode
(1byte)
5.x (1byte)
Flags
W
W
W
W
W
W
W
Flags
W
R, T
W
R, T
W
Page 27 of 44