190
1 to nDI
(0xBE)
235
1 to nDO
(0xEB)
267
1 to nDO
(0x10B)
299
1
(0x12B)
300 ~ 315
(0x12C ~
1 to UDIO
0x13B)
R : 'ead
W : Write
F : "etti gs are recorded in flash by default
Notes
E : After writing DO[60] register, the data will be stored in flash.
Warning: Frequency writing to the Flash can cause it to become corrupt.
Because of the characteristics of the relay functions, it is recommended that the PWM on
ET-2260/2261/2268 series (i.e., modules with relay functions) is not used for extended periods
of time.
Copyright © 2016 ICP DAS CO., Ltd. All Rights Reserved.
Enables frequency measurement for all
DI Channels
Sets the Power-on value for all DO
Channels
Sets the Safe value for all DO Channels
Force the DI/DO Mode.
(for the ET-2254
only)
0 = Dynamic I/O type based on DO
requests.
1 = Static I/O type by configuration (web
or Modbus).
Sets the Universal DIO channels to DI or
DO Port.
(for the ET-2254 only)
300 is the CH0 address, 301 is the CH1
address, and so on.
0 = Disable
1
1 = Enable
R/W/F
(Default= 0)
0 = Off
1
1 = On
R/W/F
(Default= 0)
0 = Off
1
1 = On
R/W/F
(Default= 0)
0 = Dynamic
1
R/W
1= Static
0 = DO type
1
R/W
1= DI type