ICP DAS USA ET-2242 User Manual page 93

Ethernet i/o modules
Hide thumbs Also See for ET-2242:
Table of Contents

Advertisement

ГК Атлант Инжиниринг – официальный представитель в РФ и СНГ
+7(495)109-02-08 sales@bbrc.ru www.bbrc.ru
ET-2200 Series Ethernet I/O Modules
4xxxx: AO Address (Base 0)
Starting
Points
Address
255
1
(0xFF)
257
1
(0x101)
258
1
(0x102)
259
1
(0x103)
263
1
(0x107)
264
1
(0x108)
R : Read;
W : Write;
Notes
F : Setting is recorded in flash as default.
Warning: Frequent writing to the Flash can cause it to become corrupt.
Copyright © 2016 ICP DAS CO., Ltd. All Rights Reserved.
Description
CPU Reset Status
Sets the Host Watchdog
Timer (WDT)
Host WDT Events
Module Name
Sets the TCP Timeout
Value
Sets the System Timeout
Value
Bits per
Range
Point
1 = Reset at Power-on
2 = Reset by the WDT
16
3 = Reset using the reset
command
<5: Disabled
5 to 65535: Enabled
(units: seconds)
0: Default
If the ET-2200 series module
16
loses communication with
the host PC for more than the
period defined in the WDT
settings, the DO channels will
revert to their safe values and
the Host WDT Events Counter
will be increased by one.
Denotes how many Host WDT
16
Events have occurred since
the last CPU reset
16
Module Name
<5: Disabled
5 to 65535: Enabled
16
(units: seconds)
0: Default
<30: Disabled
30~65535: Enabled
16
(unit: second)
0: default
Access
Type
R/W
R/W/F
R/W
R
R/W/F
R/W/F
- 93 -

Advertisement

Table of Contents
loading

Table of Contents