ET-2200 Series Ethernet I/O Modules
Step 4: Configure the I/O Pair connection on the ET-2260 #2 module
1. In the eSearch Utility, select ET-2260 #2 module and then click the Web
browser program and connect to the web server.
2. Enter the password in the Login password field (the default password is Ad i
click the "u
it button to display the configuration page.
3. Click the Pair Co
Refer to Figures 5-1.3 to 5-1.4 for illustrations of how to perform the above procedure.
4. In the I/O Pair-connection Settings , select PSUH fro the Mode drop-down options.
5. Enter the IP address for remote slave device (e.g., PETL-7060) in the Remote IP field.
6. Enter the TCP Port for remote slave device (e.g., PETL-7060) in the Remote Port field.
7. Enter a DI Count Value for ET-2260 #2 module i the DI Count field (Local DI to Remote DO).
For example, enter 2 in the DI Cou t field. This means DI x2 of the ET-2260 #2 module is
mapped to DO x2 of the PETL-7060 module.
8. Enter the DO address for remote slave device (e.g., PETL-7060) i the DO Addr field (Local DI
to Remote DO).
For example, enter 2 in the DO Addr field. This means DO addresses DO2 and DO3 of the
PETL-7060 module are mapped to DI x2 of ET-2260 #2 module.
9. Select Modbus protocol (e.g., TCP ) from the TCP/UDP drop-down options.
10. Cli k the Submit
Copyright © 2016 ICP DAS CO., Ltd. All Rights Reserved.
e tio
tab to display the I/O Pair-connection Settings page.
utto to o plete the o figuratio .
utto to lau h the
, and then
Figure 5-4.4