Installation - Southbend P36N-III Owner's Manual

Table of Contents

Advertisement

P
S
R
LATINUM
ERIES
ANGE
I
NSTALLATION
These installation procedures must be followed by qualified personnel or warranty will be void.
Local codes regarding installation vary greatly from one area to another. The National Fire Protection Association,
Inc., states in its NFPA 96 latest edition that local codes are the "authority having jurisdiction" when it comes to
installation requirements for equipment. Therefore, installations should comply with all local codes.
The installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1, Natural Gas Installation Code, CAN/CGA-B149.1, or the Propane Installation Code CAN/CGA-B149.2,
as applicable, including:
1. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of 1/2 psi (3.45 kPa).
2. The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.45 kPa).
In the Commonwealth of Massachusetts all gas appliances vented by either mechanical systems or ventilation hoods
shall comply with 248 CMR interlocking requirements.
This installation procedure does NOT cover Southbend sectional fryers, fryer filter systems, salamander broilers, upright
broilers, cheese melters, or refrigerated bases. Consult the manuals of those appliances when they are being installed as
part of a sectional range battery.
S
U
TEP 1:
NPACKING
All containers should be examined for damage before and during unloading. The freight carrier has assumed
responsibility for its safe transit and delivery. If damaged equipment is received, either apparent or concealed, a claim
must be made with the delivering carrier.
Apparent damage or loss must be noted on the freight bill at the time of delivery. The freight bill must then be signed
by the carrier representative (Driver). If the bill is not signed, the carrier may refuse the claim. The carrier can supply
the necessary forms.
A request for inspection must be made to the carrier within 15 days if there is concealed damage or loss that is
not apparent until after the equipment is uncrated. The carrier should arrange an inspection. Be certain to hold all
contents plus all packing material.
For each section, do the following:
1. Cut the banding straps and remove the corrugated cardboard surrounding the section. (If legs, casters, a flue riser,
and/or shelf components were shipped in the same container, set them aside for installation in later steps of this
procedure. Do not remove any tags or labels attached to the range until the range is installed and working properly.
2. Cut the banding strap holding the range to the wooden skid.
3. Unbolt the shipping hold-down brackets from the skid, then remove the brackets from the appliance (see Figure 12).
4. If the range is to be installed on 6" legs, go to Step 2a.
If the range is to be installed on 6" casters, go to Step 2b.
If the range is to be installed on a caster-frame, go to Step 2c.
OWNER'S MANUAL 1185836 REV 9 (10/16)
IMMEDIATELY INSPECT FOR SHIPPING DAMAGE
NOTICE
NOTICE
I
NSTALLATION
23
PAGE
OF 57

Advertisement

Table of Contents
loading

Table of Contents