7.8 #700-2 Series Horizontal Flex Vent Termination Kit

IMPORTANT: The flex pipe is permanently attached to the exterior plate. DO NOT ATTACH either #745-2 or #718-2 termina-
tion kit to fireplace (or extension kit) until it has been passed through the framed opening. Install termination plates to the
outside wall exterior.
IMPORTANT: The minimum bend radius to center is 6" (152mm) required for installation of the flexible vent pipe. Care
should be taken when installing to avoid a tight bend that may cause abrasion or damage to the flexible pipe.
The vertical vent heat shield must be installed. See Section 7.2.
7.8.1 700-WPT Installation Instructions
IMPORTANT: The heat shield within the wall thimble must overlap a minimum of 1-1/2" (38mm). An extension will be need-
ed if going through a thicker wall than 6-1/2" (165mm). Refer to BDM vent manufacturer if wall extension is necessary.

Hand bend the (2) tabs on the top of the wall pass through at the 1" (25mm) top clearance. Hand bend the (6) tabs on
the sides and bottom of the wall pass through. Repeat for other section.

From the interior, install one section of the wall pass through. Secure with (4) screws (not provided).

From the exterior, install the other section of the wall pass through, overlapping the heat shields as necessary to accom-
modate wall thickness. The section must overlap a minimum of 1-1/2" (38mm). Secure to exterior wall with (4) screws
(not provided).

Follow vent manufacturer installation instructions for vent installation.
Figure 7.8 - WPT
Hussong Mfg. Co, Inc.
SP-41, PFS Report No. 19-561
40
Rev. 9 - November 2023