5.5 Connection terminals
The descriptions and terminal overviews in this section apply to
both single-phase and three-phase motors.
For maximum torques, see section
5.5.1 Connection terminals, advanced functional module, FM
300
The advanced module has these connections:
•
three analog inputs
The factory-fitted analogue differential-pressure DPI sensor
for TPE Series 2000 is connected to one of these inputs.
•
one analog output
•
two dedicated digital inputs
•
two configurable digital inputs or open-collector outputs
•
input and output for Grundfos Digital Sensor
Not applicable for NBE, NBSE, NKE, TPE, TPED pumps. The
factory-fitted digital differential-pressure DPS sensor for NBE,
NBSE, NKE, TPE, TPED Series 2000 is connected to this
input.
•
two Pt100/1000 inputs
•
two LiqTec sensor inputs
•
two signal relay outputs
•
GENIbus connection.
See fig. 8.
Digital input 1 is factory-set to be start-stop input
where open circuit results in stop. A jumper has been
factory-fitted between terminals 2 and 6. Remove the
jumper if digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
Death or serious personal injury
- Make sure that the wires to be connected to the
connection groups below are separated from each
other by reinforced insulation in their entire
lengths.
•
Inputs and outputs
All inputs and outputs are internally separated from the
mains-conducting parts by reinforced insulation and
galvanically separated from other circuits.
All control terminals are supplied by protective extra-low
voltage, PELV, thus ensuring protection against electric shock.
•
Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250 VAC.
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
27.1
Torques.
•
Mains supply, terminals N, PE, L or L1, L2, L3, PE.
OC
DI
+24 V*
+24 V*
+24 V*/5 V*
+24 V*
OC
+24 V*
GND
+24 V*
+24 V*
+24 V*/5 V*
+
+
+24 V*
+24 V*
+24 V*/5 V*
* If you use an external supply source, make sure that there is a
connection to GND.
Fig. 8
Connection terminals, FM 300
NC
C1
NO
NC
C2
NO
18
GND
11
DI4/OC2
19
Pt100/1000
17
Pt100/1000
12
AO
GND
9
+5 V*
14
AI3
1
DI2
21
LiqTec
20
GND
22
LiqTec
DI
10
DI3/OC1
4
AI1
2
DI1
5
+5 V
6
GND
A
GENIbus A
Y
GENIbus Y
B
GENIbus B
3
GND
15
+24 V
8
+24 V
26
+5 V
23
GND
25
GDS TX
24
GDS RX
+5 V*
7
AI2
9