5.5 Connection terminals

The descriptions and terminal overviews in this section apply to
both single-phase and three-phase motors.
For maximum torques, see section
5.5.1 Connection terminals, advanced functional module, FM
300
The advanced module has these connections:
three analog inputs
The factory-fitted analogue differential-pressure DPI sensor
for TPE Series 2000 is connected to one of these inputs.
one analog output
two dedicated digital inputs
two configurable digital inputs or open-collector outputs
input and output for Grundfos Digital Sensor
Not applicable for NBE, NBSE, NKE, TPE, TPED pumps. The
factory-fitted digital differential-pressure DPS sensor for NBE,
NBSE, NKE, TPE, TPED Series 2000 is connected to this
input.
two Pt100/1000 inputs
two LiqTec sensor inputs
two signal relay outputs
GENIbus connection.
See fig. 8.
Digital input 1 is factory-set to be start-stop input
where open circuit results in stop. A jumper has been
factory-fitted between terminals 2 and 6. Remove the
jumper if digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
Death or serious personal injury
- Make sure that the wires to be connected to the
connection groups below are separated from each
other by reinforced insulation in their entire
lengths.
Inputs and outputs
All inputs and outputs are internally separated from the
mains-conducting parts by reinforced insulation and
galvanically separated from other circuits.
All control terminals are supplied by protective extra-low
voltage, PELV, thus ensuring protection against electric shock.
Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250 VAC.
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
27.1
Torques.
Mains supply, terminals N, PE, L or L1, L2, L3, PE.
OC
DI
+24 V*
+24 V*
+24 V*/5 V*
+24 V*
OC
+24 V*
GND
+24 V*
+24 V*
+24 V*/5 V*
+
+
+24 V*
+24 V*
+24 V*/5 V*
* If you use an external supply source, make sure that there is a
connection to GND.
Fig. 8
Connection terminals, FM 300
NC
C1
NO
NC
C2
NO
18
GND
11
DI4/OC2
19
Pt100/1000
17
Pt100/1000
12
AO
GND
9
+5 V*
14
AI3
1
DI2
21
LiqTec
20
GND
22
LiqTec
DI
10
DI3/OC1
4
AI1
2
DI1
5
+5 V
6
GND
A
GENIbus A
Y
GENIbus Y
B
GENIbus B
3
GND
15
+24 V
8
+24 V
26
+5 V
23
GND
25
GDS TX
24
GDS RX
+5 V*
7
AI2
9