11.16.1 Setpoint influence
Pump variant
NBE, NBSE, NKE, TPE, TPED
NBE, NBSE, NKE, TPE, TPED
Series 2000
The table below gives an overview of the types of setpoint
influence and the availability depending on pump type.
Setpoint influence
Not active
Linear function
Linear with Stop
Influence table
You can select these functions:
Not active
When set to Not active, the setpoint is not influenced from any
external function.
Linear function
The setpoint is influenced linearly from 0 to 100 %. See fig. 48.
Setpoint influence [%]
100
0
0
0.5
0
0
0
4
-50
Fig. 48 Linear function
Setpoint influence
Pump type
NBE, NBSE,
NBE, NBSE,
NKE, TPE,
NKE, TPE,
TPED Series
TPED
2000
External
100 %
3.5 V
input
5 V
10 V
20 mA
20 mA
204 C
Linear with Stop
– In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump changes to
operating mode Stop. If the input signal is above 15 %, the
operating mode is changed back to Normal. See fig. 49.
Setpoint influence [%]
100
0
0
20
0.5
0
0
0
4
-50
Normal
Stop
Fig. 49 Linear with Stop
Influence table
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
Setpoint influence [%]
100
0
0
0.5
0
0
0
4
-50
Fig. 50 Influence table, example with five points
Before the Digital inputs can be enabled, set one of
the analog inputs or Pt100/1000 inputs to External
setpoint function.
Analog inputs
See sections
11.7
Pt100/1000 inputs
11.9
External
100 %
3.5 V
input
5 V
10 V
20 mA
20 mA
204 C
External
100 %
3.5 V
input
5 V
10 V
20 mA
20 mA
204 C