Altherma low temperature monobloc backup heater (8 pages)
Summary of Contents for Daikin Altherma EBLQ011CAV3
Page 1
Service manual Daikin Altherma – Monobloc EBLQ011~016CAV3 EBLQ011~016CAW1 EDLQ011~016CAV3 EDLQ011~016CAW1 EBLQ011~016CA3V3 EBLQ011~016CA3W1 EDLQ011~016CA3V3 EDLQ011~016CA3W1 EKCB07CAV3 EK2CB07CAV3 Service manual EKMBUHCA3V3 English Daikin Altherma – Monobloc EKMBUHCA9W1...
Page 2
Disclaimer The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein.
11 Perform a check of the hydro PCB. See "2.14 Hydro PCB" on page 58. 9 Perform a check of the 3-way valve. See "2.1 3-way valve" on page 35. Possible cause: Faulty hydro PCB. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
13 Perform a check of the booster heater. See "2.6 Booster "2.23 Thermistors" on page 82. heater" on page 49. Possible cause: Faulty booster heater. Possible cause: Faulty outlet water thermistor. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
It is recommended to perform the checks in the listed or domestic hot order. water. 1 Check the water circuit for an external heat source. See "3.3 Water circuit" on page 95. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Automatic reset after INFORMATION Q3L in mixed circuit operating. reset of thermal It is recommended to perform the checks in the listed is activated. protector. order. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
3 Perform a check of the air purge valves. See "3.3 Water temperature reaches circuit" on page 95. 59.5°C (saturated condensing Possible cause: Air in the water circuit. temperature), 15 times in 300 minutes. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
3 Perform a check of the hydro PCB. See "2.14 Hydro PCB" on tank. See "3.1 Power supply" on page 91. page 58. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Possible cause: Water flow is too low. page 58. 3 Perform a check of the air purge valves. See "3.3 Water Possible cause: Faulty hydro PCB. circuit" on page 95. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
(measured pressure >38 bar) occurs 16 To solve the error code times within INFORMATION 300 minutes. It is recommended to perform the checks in the listed order. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Possible cause: operating. ▪ Faulty or disturbance of the power supply (imbalance >10%), ▪ Power drop, ▪ Short circuit. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
50°C. 1.4.36 EC-04 – Tank preheating temperature >60°C~65°C Trigger Effect Reset Unit is preheating the Unit will NOT stop Automatic reset. tank. operating. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
8 minutes: unit interface. page 50. will stop operating. Possible cause: Faulty compressor. 4 Perform a check of the reactor. See "2.20 Reactor" on page 78. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Possible cause: Faulty main PCB. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
4 Perform a check of the main PCB. See "2.17 Main PCB" on 1 Perform a check of the inverter PCB. See "2.15 Inverter page 66. PCB" on page 61. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
▪ Faulty or disturbance of the power supply (imbalance order. >10%), 1 Perform a check of the hydro PCB. See "2.14 Hydro PCB" on ▪ Power drop, page 58. ▪ Short circuit. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
3 Perform a check of the hydro PCB. See "2.14 Hydro PCB" on page 58. 1 Check the wiring between the hydro PCB and the extension PCB. See "3.1 Power supply" on page 91. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Check water pump. Replace water pump. Air purge blocked - air trapped in Component failure. Check air purge valve. Replace air purge valve. water circuit. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Bad quality/contamination of Check the water quality (odour/ Assure that quality of entering water. supply water. contamination) at cold domestic water is OK. water inlet. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Water loop temperature is too low countermeasure required. too low. (<24°C) causing ONLY the backup heater to operate. Compressor will start when water temperature reaches 24°C or more. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 26
(partial) blockage. by flow sensor, plate type heat exchanger, ▪ Check water side plate type ▪ Check the water quality. heat exchanger for blockage. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Check setting [C‑07]. Adjust setting to match application with setting [C‑07] on value 2 (= control method. - see installer reference guide. RT control). Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
(external influence) in case of in the correct position to measure interface for more accurate room temperature. room thermostat control (setting the correct room temperature. temperature measurement. [C‑07]=2). EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Displayed date/time is wrong - Daylight Saving Time NOT set Check Daylight Saving Time Set Daylight Saving Time schedules NOT correctly executed. correctly. settings. according to operation manual. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
3 Manually put the 3‑way valve in the space heating position by rotating the 3‑way valve knob. Exit Temperature Domestic hot water Same as the 3-way valve inlet EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
5 Loosen the screw. Clip 3-way valve body 6 Remove the 3‑way valve body. 7 To install 3‑way valve body, "2.1.2 Repair procedures" on page 36. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 37
3 Install the 3‑way valve motor on the 3‑way valve body. 4 Tighten the screw to fix the 3‑way valve motor to the 3‑way valve body. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
To perform a mechanical check of the 4-way valve Skip the next step of this Prerequisite: Turn OFF the unit via the user interface. procedure. Prerequisite: Turn OFF the respective circuit breaker. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
4‑way valve body 2 Cut all tie straps that fix the 4‑way valve coil harness. 3 Disconnect the 4‑way valve coil connector from the main PCB. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
5 Add refrigerant to the refrigerant circuit, see "3.2.2 Repair procedures" on page 93. Prerequisite: Turn OFF the unit via the user interface. Prerequisite: Turn OFF the respective circuit breaker. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Return to the troubleshooting of voltage measurements before, on and after each contactor the specific error and continue MUST be the same. with the next procedure. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 42
NOTICE The info above is an example of how to operate. Check the wiring diagram for correct backup heater terminals, see "5.2 Wiring diagram" on page 101. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 43
Check the condition of the O-rings and replace if needed. Apply water to the O-rings before installation. 2 Install the lower backup heater coupling and install the clip. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 44
3 Install the backup heater thermal protector sensor in the backup the next procedure. heater. To remove the backup heater contactors Prerequisite: Turn OFF the unit via the user interface. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
8 Check if the fuse of the backup heater has tripped. 2 Open all circuit breakers. CAUTION To prevent damage to the unit, all fuses MUST be opened before using a Megger. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 46
9 Separate the lower backup heater coupling. Prerequisite: Remove the required plate work. 1 Drain water from the water circuit, see "3.3.2 Repair procedures" on page 96. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 47
Backup heater pipe Prerequisite: Turn off the respective circuit breaker of the unit and Backup heater coupling the backup heater. Prerequisite: Remove the required plate work. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Backup heater thermal protector sensor Prerequisite: Turn OFF the unit via the user interface. Backup heater Prerequisite: Turn OFF the respective circuit breaker. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Install and tighten the 2 screws. with the next procedure. 4 Install the backup heater thermal protector bracket on the switch box. Install and tighten the 2 screws. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
3 Remove the cover of the compressor wire terminals. Compressor wire terminals cover 4 Disconnect the Faston connectors from the compressor wire terminals U, V and W. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
The measured insulation resistance MUST be 5 Remove the 3 nuts and remove the compressor from the unit. >3 MΩ. ▪ U–ground, ▪ V–ground, ▪ W–ground. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
4 Wrap a wet rag around the compressor pipes and solder the the specific error and continue compressor pipes to the refrigerant pipes. with the next procedure. Replace the crankcase heater, "2.9.2 Repair procedures" on page 53. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
When reconnecting a connector to the PCB, do NOT apply Is the problem solved? Action force, as this may damage the connector or connector pins No further actions required. of the PCB. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Prerequisite: Turn OFF the respective circuit breaker. PCB. Prerequisite: Remove the required plate work, see "2.19 Plate 3 Connect the expansion valve motor connector to the main PCB. work" on page 77. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
2 Latch the PCB supports using a small pliers to fix the extension PCB. 3 Connect all connectors and ground wire to the extension PCB. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
To perform a power check of the hydro PCB 1 Measure the voltage on the connector X26A on the PCB. The measured voltage MUST be 230 V AC. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 59
To check the fuse of the hydro PCB 1 Measure the continuity of the fuse. If no continuity is measured, the fuse is blown. HAP LED EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
2 Carefully pull the hydro PCB and unlatch the PCB supports one PCB. by one using a small pliers. 3 Connect all connectors and ground wire to the hydro PCB. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
4 Connect the Faston connectors to the Inverter Analyzer (SPP Make sure the fuse is plugged‑in correctly (contact with the number 1368521). fuse holder). EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
12 Press the switch BS3 once. The LED status should be as follows: 13 All LED’s on the Inverter Analyzer must lit. 14 Turn off the respective circuit breaker. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 63
8 Press the switch BS2 twice. The LED status should be as the next procedure. follows: Adjust the wiring of the inverter PCB, see "Repair procedures" on page 64. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 64
9 Cut the tie straps at the rear of the main PCB mounting plate to improve manoeuvrability of the main PCB mounting plate. 10 Lift the main PCB mounting plate and place it on a support. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 65
Is the problem solved? Action No further actions required. Return to "Checking procedures" on page 62 of the inverter PCB and continue with the next procedure. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Select the correct type. procedures" on page 66 of the LAN adapter PCB and continue with the next procedure. Replace the LAN adapter PCB, "2.16.2 Repair procedures" on page 66. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
2 Enter the model name of your unit and check if the installed spare part number corresponds with the spare part number indicated in the webbank. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 68
11 Slightly lift the upper assembly and slide it to the right to release 10 Insert 2 flathead screwdrivers in the slots and unlatch the upper the 3 hooks. and lower assemblies. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 69
X32A and X111A from the main PCB. Connector X12A Connector X21A 15 Loosen the wire terminals NA, LA , LB and NB. Connector X22A EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 70
6 Install the upper assembly on the lower assembly and slide it to the left to hook and latch the upper and lower assemblies. Upper assembly Lower assembly Hook Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
1 Adjust the wiring according to the wiring diagram and connection diagram, see "5.2 Wiring diagram" on page 101. 2 Check that all connectors are fully plugged‑in. All colour codes MUST correspond. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 72
Is the wiring on the main PCB Action correct? Return to "Checking procedures" on page 71 of the main PCB and continue with the next procedure. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
4 Connect all connectors to the main PCB assembly. 1 Check the state of the propeller fan blade assemblies for damage, deformations and cracks. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 74
PCB. The voltage MUST be 3 Measure the voltage on the DC fan motor connector pins 4-7. 270~330 V DC. The measured voltage MUST be 270~330 V DC. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
After all checking procedures listed above have been performed: Is the problem solved? Action No further actions required. Return to the troubleshooting of the specific error and continue with the next procedure. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 76
Is the problem solved? Action No further actions required. Return to "2.18.1 Checking procedures" on page 73 of the outdoor unit fan motor and continue with the next procedure. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
This procedure is just an example and may differ on some details for your actual unit. Prerequisite: Turn OFF the unit via the user interface. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
The reactor will trip at a temperature of 115°C and will reset at a temperature of 95°C. 3 Measure the resistance on the following locations of the reactor. Resistance values MUST be as follows: Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Prerequisite: Turn OFF the unit via the user interface. 37.13 Prerequisite: Turn OFF the respective circuit breaker. 38.56 39.98 Prerequisite: Remove the required plate work, see "2.19 Plate work" on page 77. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
5 Fix the refrigerant pressure sensor harness using new tie straps. 6 Add refrigerant according requirements, "3.2.2 Repair procedures" on page 93. Is the problem solved? Action No further actions required. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Prerequisite: If needed, remove any parts to create more space for the removal. 1 Remove solenoid valve coil, "2.22.2 Repair procedures" on page 81. 2 Cut the solenoid valve body pipes using a pipe cutter. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
3 Determine the thermistor resistance that matches the measured temperature. Prerequisite: Turn OFF the respective circuit breaker. Prerequisite: Remove the required plate work, see "2.19 Plate work" on page 77. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 83
Measured resistance: 21.86 kΩ, ▪ Measured resistance value is inside the range. R1T thermistor passes the check. INFORMATION All thermistors have a resistance tolerance of 5%. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Is the thermistor correctly Action installed (thermal contact between the thermistor and the piping)? Perform an electrical check of the specific thermistor, see "Checking procedures" on page 84. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 85
NOT correct on the user interface display, replace the applicable PCB. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 86
When reconnecting a connector to the PCB, do NOT apply Insulation force, as this may damage the connector or connector pins Thermistor wire Clip of the PCB. Thermistor Thermistor holder Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
6 Using the graphic below, determine the expected sensor output Tool. Re-install the software with the Updater Tool if versions do voltage based on the displayed flow rate. NOT match. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
"3.3.2 Repair procedures" on page 96. INFORMATION 2 Loosen the water flow sensor connector nut. The flow sensor connector MUST be plugged into X4A on hydro PCB. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Water flow sensor connector nut Clip Rotor shaft Water flow sensor Water pump motor 2 Inspect the rotor of the water pump motor. It MUST rotate smoothly. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Is the problem solved? Action No further actions required. Return to "2.26.1 Checking procedures" on page 89 of the water pump and continue with the next procedure. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Return to the troubleshooting of the specific error and continue with the next procedure. Adjust the wiring where needed, "3.1.2 Repair procedures" on page 92. Connector Water pump housing EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Liquid stop valve Gas stop valve Add or recuperate refrigerant until correctly charged, see 2 Check if the stop valve is completely open. "3.2.2 Repair procedures" on page 93. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
To open the stop valve of the refrigerant circuit Prerequisite: Remove the required plate work, see "2.19 Plate work" on page 77. 1 Remove the caps. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 94
▪ Flush the piping before brazing with nitrogen to avoid oxidation state. of the inside of the copper tubes (nitrogen purity ≥99.99%). ▪ R32 can be charged in gas phase. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
It is recommended to perform the checks in the listed Return to the troubleshooting of order. the specific error and continue with the next procedure. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
1 Connect the drain hose to the drain and fill valve. A leak was found in the Action installation? Repair the leak in the installation, "3.3.2 Repair procedures" on page 96. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 97
5 Purge as much air as possible from the water circuit, see "3.3.2 Repair procedures" on page 96. 6 Refill the circuit until the pressure is ±2.0 bar. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Wait for the outdoor temperature To repair the leak in the water circuit to return within the operating 1 Repair the leak in the water circuit. range. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
ALWAYS clean spilled water. 5 Clean the water filter with water and a soft brush. Water filter EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
See the installer reference guide on business portal for more information. 5.1.2 Detailed information setting mode: Remote controller See the installer reference guide on business portal for more information. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 103
# Electrical meters Backup heater element (1 kW) X*A (A4P) Connector Backup heater element (2 kW) Terminal strip Backup heater element Optional Field supply Overcurrent fuse backup heater EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 104
Control box power supply: 230 V + earth X1M: L-N-PE X1M: L-N-PE 2 core 230 V External indoor thermistor X2M: 1a-2a Power supply signal Only for KRCS01-1 4D115044A Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 105
Correct diagrams are supplied with the unit and can also be found in the technical data book. Control box X4/7M 4D115042 EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 106
Correct diagrams are supplied with the unit and can also be found in the technical data book. Backup heater kit X14M X15M 4D115042 Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 107
2 3 4 X106A X107A X22A X21A X17A Front Position of compressor terminal S1NPH M1F MS M2F MS Injection Main Upper fan Lower fan 4D115042 EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 108
H1P H2P H3P H4P H5P H6P H7P Z7C N=5 X516A X517A Z8C N=6 M1F MS M2F MS Front Upper fan Lower fan Position of compressor terminal 4D115042 Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 110
X2M/12 X2M/13 X2M/14 X2M/15 Control box X14M X14M i t p y l n r o f i t p 9 * ( 4D115042 Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 111
Min. load 10mA Min. load 10mA External indoor ambient Electric pulse meter inputs: sensor option 5 V DC pulse detection (voltage supplied by PCB) 4D115042 EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 115
Control box power supply: 230 V + earth X1M: L-N-PE X1M: L-N-PE 2 core 230 V External indoor thermistor X2M: 1a-2a Power supply signal Only for KRCS01-1 4D115044A EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 116
Correct diagrams are supplied with the unit and can also be found in the technical data book. Control box X4/7M 4D115042 Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 117
Correct diagrams are supplied with the unit and can also be found in the technical data book. Backup heater kit X14M X15M 4D115042 EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 118
2 3 4 X22A X21A X17A X106A X107A Front Position of compressor terminal S1NPH M1F MS M2F MS Injection Main Upper fan Lower fan 4D115042 Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 119
H1P H2P H3P H4P H5P H6P H7P Z7C N=5 X516A X517A Z8C N=6 M1F MS M2F MS Front Upper fan Lower fan Position of compressor terminal 4D115042 EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 121
X2M/12 X2M/13 X2M/14 X2M/15 Control box X14M X14M i t p y l n r o f i t p 9 * ( 4D115042 EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 122
Min. load 10mA Min. load 10mA External indoor ambient Electric pulse meter inputs: sensor option 5 V DC pulse detection 4D115042 (voltage supplied by PCB) Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
5 Technical data Field information report See next page. Service manual EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 129
In case a problem occurred on the unit which could not be resolved by using the content of this service manual or in case you have a problem which could be resolved but of which the manufacturer should be notified, we advise you to contact your distributor. To facilitate the investigation, additional information is required.
Page 130
Application information Application (house, apartment, office,…): New project or reimbursement: Heat emitters (radiators / under floor heating / fan coils /…): Hydraulic layout (simple schematic): Unit / Installation information Model name: Serial number: Installation / commissioning date: Software version hydro PCB A1P Software version hydro PCB A5P Software version user interface: Software version outdoor PCB:...
Also additional information on the service tools (instruction, latest software) can be found here. Field settings See next page. EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1 Service manual + EK(2)CB07CAV3 + EKMBUHCA3V3+9W1 Daikin Altherma – Monobloc ESIE18-04 – 2019.02...
Page 133
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value User settings └─ Preset values └─ Room temperature 7.4.1.1 Comfort (heating) [3-07]~[3-06], step: A.3.2.4 21°C 7.4.1.2 Eco (heating) [3-07]~[3-06], step: A.3.2.4 19°C 7.4.1.3 Comfort (cooling)
Page 134
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value A.2.1.8 [7-02] Number of LWT zones 0: 1 LWT zone 1: 2 LWT zones A.2.1.9 [F-0D] Pump operation mode 0: Continuous 1: Sample 2: Request...
Page 135
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value A.3.1.3.2 [9-0A] Cooling 3~10°C, step: 1°C 5°C └─ Room thermostat A.3.2.1.1 [3-07] Room temp. range Minimum temp (heating) 12~18°C, step: A.3.2.4 16°C A.3.2.1.2 [3-06]...
Page 136
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value A.6.C 0: Manual 1: Automatic └─ Overview settings [0-00] Leaving water value for high ambient temp. for LWT add zone heating WD curve. [9-05]~min(45, [9-06])°C, step: 1°C 35⁰C [0-01]...
Page 137
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [4-03] Operation permission of the booster heater 0: Limited 1: No limit 2: Most optimum 3: Optimum 4: Only legionella [4-04] How to protect the water pipes from freezing 0: Continuous pump operation...
Page 138
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [8-06] Leaving water temperature maximum modulation. 0~10°C, step: 1°C 3°C [8-07] What is the desired comfort main LWT in cooling? [9-03]~[9-02], step: 1°C 18°C [8-08]...
Page 139
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [D-04] Is the option box used for PCC ? 0: No 1: Yes [D-05] Is the pump allowed to run if prefer. kWh rate PS is cut? 0: Forced off 1: As normal [D-07]...
Need help?
Do you have a question about the Altherma EBLQ011CAV3 and is the answer not in the manual?
Questions and answers