Expansion Valve; Checking Procedures; Repair Procedures - Daikin Altherma EBLQ011CAV3 Service Manual

Monobloc
Hide thumbs Also See for Altherma EBLQ011CAV3:
Table of Contents

Advertisement

2 Components
Is the problem solved?
No
2.11

Expansion valve

2.11.1

Checking procedures

INFORMATION
It is recommended to perform the checks in the listed
order.
To perform a mechanical check of the expansion
valve
Prerequisite: Power OFF the unit for 3 minutes. Then turn ON the
unit and listen to the expansion valve assembly. If the expansion
valve does NOT make a latching sound, continue with the electrical
check of the expansion valve, see
page 54.
Prerequisite: Turn OFF the unit via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
work" on
page 77.
1 Remove the expansion valve motor from the expansion valve
body, see
"2.11.2 Repair procedures" on
2 Slide the magnet (tool part number 9950038) over the
expansion valve body and gently rotate the magnet clockwise/
counterclockwise to manually close/open the expansion valve
body.
Does the expansion valve
body open?
Yes
No
To perform an electrical check of the expansion
valve
Prerequisite: First perform a mechanical check of the expansion
valve, see
"2.11.1 Checking procedures" on
1 Make sure that the electrical connector of the expansion valve
motor is correctly connected to the main PCB.
2 Disconnect the electrical connector of the expansion valve
motor from the main PCB and measure the continuity between
the following pins (windings) using a multi meter. All
measurements MUST be approximately the same.
▪ Connector pin 1‑6,
▪ Connector pin 2‑6,
▪ Connector pin 3‑6,
▪ Connector pin 4‑6.
Service manual
54
Action
Return to the troubleshooting of
the specific error and continue
with the next procedure.
"2.11.1 Checking procedures" on
"2.19  Plate
page 54.
Action
Perform an electrical check of the
expansion valve, see
"2.11.1 Checking procedures" on
page 54.
Replace the expansion valve
body, see
"2.11.2 Repair
procedures" on
page 54.
page 54.
a
a
Connector S20
1 or more windings have no
continuity?
Yes
No
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Yes
No
2.11.2

Repair procedures

To remove the expansion valve motor
Prerequisite: Turn OFF the unit via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
work" on
page 77.
Prerequisite: If needed, remove any parts to create more space for
the removal.
1 Pull up the expansion valve motor to remove it from the
expansion valve body.
INFORMATION
It may be needed to turn the expansion valve motor 1/8
turn counter clockwise to unlock it.
a
Expansion valve motor
b
Expansion valve motor harness
EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1
+ EK(2)CB07CAV3 + EKMBUHCA3V3+9W1
Action
Replace the expansion valve
motor,
"2.11.2 Repair
procedures" on
page 54.
Component is OK. Return to the
troubleshooting of the specific
error and continue with the next
step.
Action
No further actions required.
Return to the troubleshooting of
the specific error and continue
with the next procedure.
"2.19  Plate
a
b
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02