Daikin EBLQ011CA3V3 Installer's Reference Manual
Hide thumbs Also See for EBLQ011CA3V3:
Table of Contents

Advertisement

Installer reference guide
Daikin Altherma low temperature monobloc
EBLQ011CA3V3
EBLQ014CA3V3
EBLQ016CA3V3
EBLQ011CA3W1
EBLQ014CA3W1
EBLQ016CA3W1
EDLQ011CA3V3
EDLQ014CA3V3
EDLQ016CA3V3
EDLQ011CA3W1
EDLQ014CA3W1
EDLQ016CA3W1
Installer reference guide
EKCB07CAV3
English
Daikin Altherma low temperature monobloc
EK2CB07CAV3

Advertisement

Table of Contents
loading

Summary of Contents for Daikin EBLQ011CA3V3

  • Page 1 Installer reference guide Daikin Altherma low temperature monobloc EBLQ011CA3V3 EBLQ014CA3V3 EBLQ016CA3V3 EBLQ011CA3W1 EBLQ014CA3W1 EBLQ016CA3W1 EDLQ011CA3V3 EDLQ014CA3V3 EDLQ016CA3V3 EDLQ011CA3W1 EDLQ014CA3W1 EDLQ016CA3W1 Installer reference guide EKCB07CAV3 English Daikin Altherma low temperature monobloc EK2CB07CAV3...
  • Page 2: Table Of Contents

    7.7.16 To connect the electrical meters ........40 6.2.1 Installation site requirements of the outdoor unit ..21 7.7.17 To connect the alarm output ........41 Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 3: General Safety Precautions

    Symptom: The compressor does NOT start (space injury. heating or domestic water heating)......73 12.3.3 Symptom: The pump is making noise (cavitation) ..73 12.3.4 Symptom: The pressure relief valve opens....74 EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 4: For The Installer

    (on top of the ▪ In places where there is a risk of fire due to the leakage of instructions described in the Daikin documentation). flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
  • Page 5: Brine

    ▪ Charge the refrigerant in liquid form. Adding it in gas form may providing full disconnection under overvoltage category  III prevent normal operation. condition, MUST be installed in the fixed wiring. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 6: About The Documentation

    Daikin website (publicly accessible). ▪ Over-tightening the terminal screws may break them. ▪ The full set of latest technical data is available on the Daikin extranet (authentication required). Install power cables at least 1 metre away from televisions or radios to prevent interference.
  • Page 7: Installation

    3.2.3 To remove the accessories from the Outdoor unit outdoor unit 1 Open the outdoor unit. 3.2.1 To unpack the outdoor unit EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 8: Control Box

    ▪ To be able to use the option box, it is required that 3.3.1 To unpack the control box optional control box EKCB07CAV3 is part of the system. 3.4.1 To unpack the option box Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 9: To Remove The Accessories From The Option Box

    When installing or servicing several units at the same time, Optional make sure NOT to switch the service panels between different models. Control box Capacity class Model series EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 10: Combining Units And Options

    The user interface and a possible additional user interface are heated. available as an option. ▪ To have an interface containing other languages. The additional user interface can be connected: Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 11: Possible Options For The Control Box

    For installation instructions, see "7.7.7  To connect the user Heat pump convector (FWXV) interface" on page 37. For providing space heating/cooling, it is possible to use heat pump convectors (FWXV). EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 12: Possible Options For The Option Box

    ▪ If control box EKCB07CAV3 is part of the system, you questions first: can also connect the LAN adapter to the control box. ▪ How many rooms are heated or cooled by the Daikin heat  pump LAN adapter for smartphone control (BRP069A62) system? You can install this LAN adapter to control the system via a ▪...
  • Page 13: Single Room

    ▪ Code: [C-05] condition. thermostat. Benefits ▪ Wireless. The Daikin external room thermostat is available in a wireless version. ▪ Efficiency. Although the external room thermostat only sends ON/ OFF signals, it is specifically designed for the heat pump system. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3...
  • Page 14 ▪ Cooling. Heat  pump convectors provide, besides heating ▪ Stylish. capacity, also excellent cooling capacity. ▪ Efficiency. Under  floor heating has the best performance with Altherma LT. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 15: Multiple Rooms - One Lwt Zone

    ▪ Code: [7-02] Benefits ▪ Cost effective. You do NOT need an additional external room thermostat. ▪ Easy. Same installation as for one room, but with thermostatic valves. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 16 ▪ A shut-off valve to prevent hot water supply when the room has INFORMATION no heating demand To increase comfort and performance, Daikin recommends ▪ A shut-off valve to prevent condensation on the floor during to install the valve kit option EKVKHPC on each heat pump cooling operation of the rooms with heat pump convectors.
  • Page 17: Multiple Rooms - Two Lwt Zones

    NOTICE ▪ Main zone = Zone with the lowest design temperature in heating, Daikin is NOT responsible for the operation of the mixing and the highest design temperature in cooling valve station pump. It is the responsibility of the installer to guarantee pump operation.
  • Page 18: Setting Up The Domestic Hot Water Tank

    ▪ If energy prices are the same during the day and the night, Answer the following questions and calculate the DHW consumption Daikin recommends to heat up the DHW tank during the day. (equivalent hot water volume at 40°C) using typical water volumes: ▪...
  • Page 19: Setup And Configuration - Dhw Tank

    Heater element (field supply) Non‑return valve (field supply) The calculated produced heat and consumed energy are Shower (field supply) an estimation, the accuracy cannot be guaranteed. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 20: Produced Heat

    ALL power input of the system is covered by the of each power meter. electrical power meters. ▪ See "5.4.4  Preferential kWh rate power supply"  on page  21 an example with two power meters. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 21: Preferential Kwh Rate Power Supply

    6 Preparation ▪ If this is NOT possible, Daikin recommends to connect a remote 5.4.4 Preferential kWh rate power supply indoor sensor (option KRCS01-1). General rule ▪ Setup: ▪ Power meter 1: Measures the refrigerant part of the outdoor unit. ▪ Requires...
  • Page 22: Additional Installation Site Requirements Of The Outdoor Unit In Cold Climates

    ▪ Where the voltage fluctuates a lot ▪ In vehicles or vessels ▪ Where acidic or alkaline vapour is present Snow cover or shed Pedestal Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 23: Installation Site Requirements Of The Control Box

    ▪ Piping length. It is recommended to avoid long runs of piping between the domestic hot water tank and the hot water end point (shower, bath,…) and to avoid dead ends. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 24: Formula To Calculate The Expansion Vessel Pre-Pressure

    ▪ Air vents. Provide air vents at all high points of the system, which must also be easily accessible for servicing. The outdoor unit has a manual air purge valve. The backup heater (option) has an Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 25: To Check The Water Volume And Flow Rate

    7H will be generated (no heating or operation). Minimum required flow rate 20 l/min See the recommended procedure as described in "9.4  Checklist during commissioning" on page 67. Pre-pressure (bar) Maximum water volume (l) EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 26: Changing The Pre-Pressure Of The Expansion Vessel

    6.4.1 About preparing electrical wiring 6.4.3 Overview of electrical connections except INFORMATION external actuators Also read the precautions and requirements in the "General safety precautions" chapter. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 27: Overview Of Electrical Connections For External And Internal Actuators

    3 (of which 2 are for valve kit shared with those EKMBHBP1 (between of item 10) outdoor unit and control box) User interface User interface Optional equipment Outdoor unit EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 28: Overview: Installation

    Remote indoor sensor Field-supplied components Electric meter 2 (per meter) Alarm output Space cooling/heating ON/OFF output Changeover to external heat source Cable section 2.5 mm². Minimum cable section 0.75 mm². Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 29: To Open The Switch Box Cover Of The Outdoor Unit

    Failure to follow this warning may result in electric shock. INFORMATION Do NOT remove the plugs from the front plate of the option 3× box. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 30: Mounting The Outdoor Unit

    CANNOT freeze. (mm) Make sure not to cover the drain holes. INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 31: To Prevent The Outdoor Unit From Falling Over

    (field supply). box. For more information, refer to "7.7.7  To connect the user interface" on page 37. 4 Attach the ends of the cables and tighten them. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 32: Mounting The Option Box

    10 bar must be installed on the Filling the domestic hot water tank (if applicable). domestic cold water inlet connection in accordance with Insulating the water piping. the applicable legislation. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 33: To Protect The Water Circuit Against Freezing

    ▪ Protection against freezing: the glycol will prevent the liquid inside the piping from freezing. Lowest expected Prevent from Prevent from outdoor bursting freezing temperature –5°C –10°C –15°C –20°C — –25°C — EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 34: To Fill The Water Circuit

    However, at all times water pressure shall remain above DANGER: RISK OF ELECTROCUTION 1 bar to avoid air entering the circuit. WARNING ALWAYS use multicore cable for power supply cables. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 35: Guidelines When Connecting The Electrical Wiring

    "7.2.2 To open the outdoor unit" on page 28. 2 Strip insulation (20 mm) from the wires. Strip wire end to this point Excessive strip length may cause electrical shock or leakage. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 36: To Connect The Main Power Supply

    Preferential power supply contact (on the control box) INFORMATION For the exact position of connectors X6Y, X6YA, and X6YB in the switch box, see the service manual. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 37: To Connect The Backup Heater Power Supply

    For more information on the backup heater types, and for how to configure the backup heater, refer to the "Configuration" chapter of the installation manual of the outdoor unit. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 38: To Connect The Shut-Off Valve

    To connect the shut-off valve 1 Connect the valve control cable to the appropriate terminals as shown in the illustration below. NOTICE Only connect NO (normal open) valves. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 39: To Connect The Domestic Hot Water Pump

    To connect the interconnection cable between control box and outdoor unit 1 Connect X2M/22 (control box) to X5M/4 (outdoor unit). 2 Connect X2M/23 (control box) to X5M/3 (outdoor unit). EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 40: To Connect The Electrical Wiring On The Option Box

    X2M/7 and X2M/9; the negative polarity to X2M/8 and X2M/10. 1 Connect the electrical meters cable to the appropriate terminals as shown in the illustration below. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 41: To Connect The Alarm Output

    1 Connect the space cooling/heating ON/OFF output cable to the 7.10.1 To close the option box appropriate terminals as shown in the illustration below. 1 Close the front plate. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 42: Configuration

    To set the user permission level to Advanced end user 1 Go to the main menu or any of its submenus: 2 Press for more than 4 seconds. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 43: To Copy The System Settings From The First To The Second User Interface

    If a second user interface is connected, the installer must first proceed below instructions for the proper configuration of the 2 user interfaces. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 44: To Copy The Language Set From The First To The Second User Interface

    When the installer settings are changed, the system will request to confirm. When confirmation is complete, the screen will shortly turn OFF and "busy" will be displayed for several seconds. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 45 ▪ b: OFF ▪ c: On ▪ c: On ▪ d: Heating demand (by ext RT or ▪ d: Pump operation continued >> ▪ e: Pump operation EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 46: Quick Wizard: Options

    Control box INFORMATION The correct domestic hot water default settings become only applicable when domestic hot water operation is activated ([E‑05]=1). Remote outdoor sensor "5 Application guidelines" on page 12. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 47 ▪ 0 (EKHWS): DHW tank with booster heater installed at the side of the tank. (Default). ▪ 5 (EKHWP): DHW tank with booster heater installed at the top of the tank. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 48: Quick Wizard: Capacities (Energy Metering)

    Remark: This value has only meaning in room thermostat control. INFORMATION You can only connect either the remote indoor sensor or the remote outdoor sensor. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 49 : Target leaving water temperature (main) ▪ T : Target leaving water temperature ▪ T : Outdoor temperature (main) continued >> ▪ T : Outdoor temperature continued >> EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 50 [0-00] Set weather-dependent heating: [0-01] [0-02] [0-01] [0-03] [0-00] [0-03] [0-02] ▪ T : Target leaving water temperature (additional) ▪ T : Outdoor temperature continued >> Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 51 The unit will supply hot water to the heat emitters and the room will be heated. Additionally, also the desired leaving EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 52: Domestic Hot Water Control

    Minimum leaving water temperature setpoint required to reach a stable condition on the comfort setpoint for the Limit the maximum hot water temperature according to the room. applicable legislation. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 53: Contact/Helpdesk Number

    Preset leaving water temperature for the main leaving water temperature zone in case of NOT weather dependent [7.4.2.1] [8-09] Comfort (heating) [9‑01]°C~[9‑00]°C (default: 45°C) [7.4.2.2] [8-0A] Eco (heating) [9‑01]°C~[9‑00]°C (default: 40°C) EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 54 ▪ 2 (enabled) L=4°C, temperature is displayed in °C. R=4°C (−2°C<T <2°C) (default) ▪ 3 (enabled) L=2°C, R=8°C (−4°C<T <4°C) ▪ 4 (enabled) L=4°C, R=8°C (−4°C<T <4°C) Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 55 ▪ Turn ON the leaving water temperature home page. Leaving water temperature Room frost protection is NOT control ([C‑07]=0) guaranteed. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 56 22°C and in cooling 24°C, with a hysteresis value of 1°C and an offset of 4°C. Changeover from heating to cooling will occur when the room Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 57: Domestic Hot Water Control: Advanced

    The tank will then heat up until interface. these setpoint temperatures have been reached. Additionally, a EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 58 ▪ Ambient temperature is out of the operating range: <[5-03] >35°C ▪ Domestic hot water temperature is 2°C lower than the heat  pump  OFF temperature. continued >> Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 59 For more information, see the operation range. Timers for simultaneous request space and domestic hot water operation Code Description [8-00] Do not change. (default: 1) EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 60 The disinfection function settings MUST be configured by temperature [4-02] or [F-01]. the installer according to the applicable legislation. Range: 20~95 minutes (default: 50). [8-02]: Anti-recycling time Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 61: Heat Source Settings

    [A.5.1.4] [5‑01] Equilibrium temperature. Outdoor temperature below which operation of the backup heater is allowed. Range: –15°C~35°C (default: –4°C) (step: 1°C) EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 62: System Settings

    Space heating priority temperature. the auto restart function. Defines the outdoor temperature which below the domestic hot water will be heated by booster heater only. Range: –15°C~35°C (default: 0°C). Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 63 [D‑00] Booster heater Backup heater Compressor <4°C (pump will be activated for 10 minutes and deactivated after 10 minutes). Daikin shall NOT be held liable for any damage 0 (default) Forced OFF Forced OFF Forced OFF resulting this functionality.
  • Page 64 (kPa) b (l/min) b (l/min) [9-0D]=6 [9-0D]=7 a (kPa) a (kPa) b (l/min) b (l/min) [9-0D]=8 a (kPa) b (l/min) External static pressure Water flow rate Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 65: Menu Structure: Overview User Settings

    Set weather-dependent heating Set weather-dependent cooling [7.7.2] Additional Set weather-dependent heating Set weather-dependent cooling INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 66: Menu Structure: Overview Installer Settings

    [A.7] Commissioning Test run UFH screed dryout Air purge Actuator test run INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 67: Commissioning

    The fuses or locally installed protection devices are The underfloor screed dryout function is started (if installed according to this document, and have NOT been necessary). bypassed. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 68: To Check The Minimum Flow Rate

    To perform an automatic air purge Prerequisite: Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 69: To Perform A Test Run

    4 Select OK and press Result: The actuator test run starts. It automatically stops when finished. To stop it manually, press , select OK and press EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 70: 10 Hand-Over To The User

    2 Set a dryout program. ▪ Explain the user about energy saving tips as described in the 3 Select Start dryout and press operation manual. 4 Select OK and press Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 71: About Locking And Unlocking

    GWP value of the refrigerant × Total refrigerant charge [in force when you reinsert the water filter so as NOT to kg] / 1000 damage the water filter mesh. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 72: 12 Troubleshooting

    OFF. WARNING If the internal wiring is damaged, it has to be replaced by the manufacturer, its service agent or similarly qualified persons. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 73: Symptom: The Compressor Does Not Start (Space Heating Or Domestic Water Heating)

    ▪ The expansion vessel is NOT broken. ▪ The pre-pressure setting of the expansion vessel is correct (see "6.3.4  Changing the pre- pressure of the expansion vessel" on page 26). EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 74: Symptom: The Pressure Relief Valve Opens

    ▪ The water pressure ▪ Whether there is air in the system ▪ The air purge operation Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 75: Symptom: The Energy Metering (Produced Heat) Is Not Working Correctly

    OU: Malfunction of inverter Please contact your dealer. radiating fin temperature rise. OU: Compressor startup defect. Please contact your dealer. Please contact your dealer. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 76 Room temperature sensor sensor problem. problem. Please contact your dealer. Please contact your dealer. Heat exchanger frozen. Abnormal increase tank temperature. Heat exchanger frozen. Tank preheating Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 77 ▪ During anti-legionella operation (weekly), the error code occurred during space heating AH-00 is displayed because the unit cannot reach the operation. Check the space requested temperature required for tank disinfection. heating circuit. EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 78: 13 Disposal

    You can achieve this, for example, by activating all fans of the fan coil units. INFORMATION For more details, see the service manual. Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 79: 14 Technical Data

    14 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin extranet (authentication required). 14.1 Service space: Outdoor unit...
  • Page 80: Piping Diagram: Outdoor Unit

    See note *** See note *** Main terminal Upper Fan Upper fan Earth wiring Lower Fan Lower fan Field supply Injection Injection Option Main Main Switch box Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 81 (W1 only) Solenoid valve (hot gas pass) K1M~K2M (A2P) Magnetic contactor (main-upload) Z1C~Z3C (V3 Noise filter (ferrite core) (W1 only) only) K1R (A1P) Magnetic relay (Y1S) EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 82 Outdoor backup heater power supply 3-way valve for domestic hot English Translation water Only for *** Only for *** Valve kit Backup heater element (3 kW) PC (A7P) Power circuit Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 83 F2U (A4P) Fuse T 2 A 250 V for 3-way valve External indoor ambient sensor option S5P-S6P # Electrical meters X*A (A4P) Connector Terminal strip Optional Field supply EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Installer reference guide Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 84: Esp Curve: Outdoor Unit

    If glycol is added to the system, the operation range limit is lower. ▪ Selecting a flow outside the operating area can damage the unit or cause the unit to malfunction. B (l/min) 4D117234 Installer reference guide EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3 Daikin Altherma low temperature monobloc 4P538847-1 – 2018.05...
  • Page 85 Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with product according instructions accompanying documentation.
  • Page 86 Field settings table [6.8.2] = ..ID8281 (*1) (*2) [6.8.2] = ..ID8282 (*3) (*4) Applicable units EDLQ011CAV3 EDLQ011CA3V3 EDLQ014CAV3 EDLQ014CA3V3 EDLQ016CAV3 EDLQ016CA3V3 EBLQ011CAV3 EBLQ011CA3V3 EBLQ014CAV3 EBLQ014CA3V3 EBLQ016CAV3 EBLQ016CA3V3 EDLQ011CAW1 EDLQ011CA3W1 EDLQ014CAW1 EDLQ014CA3W1 EDLQ016CAW1 EDLQ016CA3W1 EBLQ011CAW1 EBLQ011CA3W1 EBLQ014CAW1 EBLQ014CA3W1 EBLQ016CAW1...
  • Page 87 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value User settings └─ Preset values └─ Room temperature 7.4.1.1 Comfort (heating) [3-07]~[3-06], step: A.3.2.4 21°C 7.4.1.2 Eco (heating) [3-07]~[3-06], step: A.3.2.4 19°C 7.4.1.3 Comfort (cooling)
  • Page 88 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value A.2.1.8 [7-02] Number of LWT zones 0: 1 LWT zone 1: 2 LWT zones A.2.1.9 [F-0D] Pump operation mode 0: Continuous 1: Sample 2: Request...
  • Page 89 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value A.3.1.3.2 [9-0A] Cooling 3~10°C, step: 1°C 5°C └─ Room thermostat A.3.2.1.1 [3-07] Room temp. range Minimum temp (heating) 12~18°C, step: A.3.2.4 16°C A.3.2.1.2 [3-06]...
  • Page 90 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value A.6.C 0: Manual 1: Automatic └─ Overview settings [0-00] Leaving water value for high ambient temp. for LWT add zone heating WD curve. [9-05]~min(45, [9-06])°C, step: 1°C 35⁰C [0-01]...
  • Page 91 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [4-03] Operation permission of the booster heater 0: Limited 1: No limit 2: Most optimum 3: Optimum 4: Only legionella [4-04] How to protect the water pipes from freezing 0: Continuous pump operation...
  • Page 92 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [8-06] Leaving water temperature maximum modulation. 0~10°C, step: 1°C 3°C [8-07] What is the desired comfort main LWT in cooling? [9-03]~[9-02], step: 1°C 18°C [8-08]...
  • Page 93 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [D-04] Is the option box used for PCC ? 0: No 1: Yes [D-05] Is the pump allowed to run if prefer. kWh rate PS is cut? 0: Forced off 1: As normal [D-07]...
  • Page 96 4P538847-1 2018.05...