5.2.2 Quick wizard: Standard..........15 Daikin website (publicly accessible). 5.2.3 Quick wizard: Options ..........16 ▪ The full set of latest technical data is available on the Daikin 5.2.4 Quick wizard: Capacities (energy metering) ....17 extranet (authentication required). 5.2.5 Space heating/cooling control........
Height of the unit including the installation structure M1...3 Individual motorised valve to control loop FHL1...3 (field Height of obstacles B and D supply) Height of installation structure below the unit EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
If valve kit EKMBHBP1 is part of the system, then the required cable section is 0.75 mm². If valve kit EKMBHBP1 is NOT part of the system, then the minimum required cable section is 0.75 mm². Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
In regions with snowfall, snow might build up and freeze between the heat exchanger and the external plate. This might decrease the operating efficiency. To prevent this: 1 Drill (a, 4×) and remove the knockout hole (b). EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
▪ Protection against freezing: the glycol will prevent the liquid inside the piping from freezing. Lowest expected Prevent from Prevent from outdoor bursting freezing temperature –5°C –10°C –15°C –20°C — –25°C — Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
To prevent the freezing of the outdoor water piping during winter time, the thickness of the sealing material MUST be at least 13 mm (with λ=0.039 W/mK). EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
▪ Shut-off valve (field supply) ▪ Domestic hot water pump (field supply) ▪ Space heat/cool operation control ▪ Main power supply Main power supply ▪ Backup heater power supply Backup heater power supply Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
1 Open the backup heater switch box (see "4.1.3 To open the backup heater switch box cover of the outdoor unit" on page 7). 2 Route the wiring as follows: EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
2 Connect the cable of the domestic hot water pump to the bottom side of control box terminals X8M/8+9. 1× 1× Notch this part for the wiring to pass through with nippers etc. Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
> Information > User permission level. ▪ "To access the installer settings" on page 13 3 Press for more than 4 seconds. ▪ "5.3 Menu structure: Overview installer settings" on page 19 Result: is displayed on the home pages. EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
(languages, schedules etc.) will be synchronised from the selected source user interface to the other one. Installer settings The system will restart. Cancel Confirm Adjust Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
4 After configuration, select Confirm layout and press Confirm layout Please confirm the system layout. The system will restart and will be ready for first startup. Cancel Confirm Adjust EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
Backup heater [E-03] [5-0D] detection of a power failure. configuration See also table below (Alarm output logic). Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
▪ T : Outdoor temperature dependent ▪ 2 (Fixed/scheduled): Absolute scheduled (only for leaving water temperature control) ▪ 3 (WD/scheduled): Weather- dependent + scheduled (only for leaving water temperature control) EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
By setting the weather‑dependent curve to a higher position, it cannot drop below the minimum setpoint. Refer to the illustration below. Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
Forced defrost Emergency [A.7] Commissioning Test run UFH screed dryout Air purge Actuator test run INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
The pressure relief valve purges water when opened. and damage the unit. The minimum water volume is guaranteed in all conditions. See "To check the water volume" in "3.2 Preparing water piping" on page 5. Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
Also avoid disturbances in the water circuit during the operation manual. test run. ▪ 2-way valve test ▪ 3-way valve test ▪ Alarm output test ▪ Cooling/heating signal test EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
4 Select Lock or Unlock, and press To activate or deactivate button lock 1 Press to go to one of the home pages. 2 Press for more than 5 seconds. Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
8 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin extranet (authentication required). Piping diagram: Outdoor unit t >...
Page 24
(W1 only) only) V2R~V3R (A1P) Diode module F8U, F9U (W1 Fuse F 1 A 250 V (V3 only) only) V3R (A2P)(W1 Diode module H1P~H7P (A2P) LED (service monitor is orange) only) (V3 only) Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
Page 25
Inlet water thermistor F2U (A4P) Fuse T 2 A 250 V for 3-way valve External outdoor ambient sensor Relay for heating Flow switch Terminal strip Power supply transformer Relay for cooling EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
Page 26
Fuse T 2 A 250 V F2U (A4P) Fuse T 2 A 250 V for 3-way valve External indoor ambient sensor option S5P-S6P # Electrical meters X*A (A4P) Connector Terminal strip Optional Field supply Installation manual EBLQ+EDLQ011~016CA3V3+W1 Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...
Page 27
3 core Control box power supply: 230 V + earth X1M: L-N-PE X1M: L-N-PE 2 core 230 V External indoor thermistor X2M: 1a-2a Power supply signal Only for KRCS01-1 4D116771-1 EBLQ+EDLQ011~016CA3V3+W1 Installation manual Daikin Altherma low temperature monobloc 4P537990-1 – 2018.05...