2.9.2

Repair procedures

To remove the crankcase heater
Prerequisite: Turn OFF the unit via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
work" on
page 77.
1 Remove the compressor sound insulation.
2 Detach the spring that fixes the crankcase heater on the
compressor.
a
a
Spring
b
Crankcase heater
3 Disconnect the crankcase heater connector from the main PCB.
4 Cut all tie straps that fix the crankcase heater harness.
5 To
install
the
crankcase
procedures" on
page 53.
To install the crankcase heater
1 Install the crankcase heater on the compressor.
2 Attach the spring to fix the crankcase heater.
a
a
Spring
b
Crankcase heater
3 Route the crankcase heater harness towards the switch box.
4 Connect the crankcase heater connector to the main PCB.
WARNING
When reconnecting a connector to the PCB, do NOT apply
force, as this may damage the connector or connector pins
of the PCB.
EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1
+ EK(2)CB07CAV3 + EKMBUHCA3V3+9W1
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02
"2.19  Plate
b
heater,
see
"2.9.2  Repair
b
5 Fix the crankcase heater harness using new tie straps.
INFORMATION
Replace all cable ties that were cut during removal.
Is the problem solved?
Yes
No
2.10

Current loop PCB

2.10.1

Checking procedures

To perform an electrical check of the current loop
PCB
Prerequisite: Turn OFF the unit via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
work" on
page 77.
1 Connect the D‑checker tool to the X10A connector on the hydro
PCB.
2 Check the communication between the extension PCB and the
hydro PCB. For example:
▪ Read out of tank temperature for monobloc unit.
3 If the communication between the extension PCB and hydro
PCB is correct, the current loop PCB is functioning correctly.
Current loop PCB is
functioning correctly?
Yes
No
2.10.2
Repair procedures
To remove the current loop PCB
Prerequisite: Turn OFF the unit via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
work" on
page 77.
1 Disconnect all connectors from the current loop PCB.
2 Carefully pull the current loop PCB and unlatch the PCB
supports one by one using a small pliers.
3 Remove the current loop PCB from the switch box.
4 To install the current loop PCB, see
procedures" on
page 53.
To install the current loop PCB
1 Install the current loop PCB in the correct location in the switch
box.
2 Latch the PCB supports using a small pliers to fix the current
loop PCB.
3 Connect all connectors to the current loop PCB.
Is the problem solved?
Yes
2 Components
Action
No further actions required.
Return to the troubleshooting of
the specific error and continue
with the next procedure.
"2.19  Plate
Action
Return to the troubleshooting of
the specific error and continue
with the next step.
Replace the current loop PCB,
see
"2.10.2 Repair
procedures" on
page 53.
"2.19  Plate
"2.10.2  Repair
Action
No further actions required.