Repair Procedures; Refrigerant Circuit; Checking Procedures - Daikin Altherma EBLQ011CAV3 Service Manual

Monobloc
Hide thumbs Also See for Altherma EBLQ011CAV3:
Table of Contents

Advertisement

3 Third party components
3.1.2

Repair procedures

To adjust the power supply
1 Make sure that the power source is in line with the requirements
described in the databook.
Is the problem solved?
Yes
No
To adjust the wiring between the hydro PCB and
extension PCB
1 Adjust the wiring according to the wiring diagram and
connection diagram, see
"5.2 Wiring diagram" on
2 Check that all connectors are fully plugged‑in. All colour codes
MUST correspond.
3 Check that no connectors are damaged.
Is the problem solved?
Yes
No
3.2

Refrigerant circuit

3.2.1

Checking procedures

INFORMATION
It is recommended to perform the checks in the listed
order.
To check if the stop valve is open
Prerequisite: Remove the required plate work, see
work" on
page 77.
1 Remove the caps.
b
a
Cap
b
Liquid stop valve
c
Gas stop valve
2 Check if the stop valve is completely open.
Service manual
92
Action
No further actions required.
Return to the troubleshooting of
the specific error and continue
with the next procedure.
page 101.
Action
No further actions required.
Return to the troubleshooting of
the specific error and continue
with the next procedure.
"2.19  Plate
c
a
a
The refrigerant circuit stop
valve is open?
Yes
No
To check if the refrigerant circuit is clogged
Prerequisite: Turn OFF the unit via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Wait for the refrigerant to reach the outdoor temperature.
2 Connect a manometer to the service port.
3 Measure the low pressure as a reference.
4 Turn ON the power of the unit.
5 Activate Cooling via the user interface.
6 Again measure the low pressure.
Low pressure lower than
expected?
Yes
No
7 Using a thermometer, check for a temperature drop of minimum
4°C. The obstruction is most likely located where this
temperature drop occurs.
Temperature drop found?
Yes
No
To check if the refrigerant circuit is correctly
charged
1 Recuperate all refrigerant from the unit, see
procedures" on
page 93.
2 Weigh the recuperated refrigerant.
3 Compare the weight of the recuperated refrigerant with the
logbook of the unit. If the weight does NOT match the logbook,
the refrigerant circuit is charged incorrectly.
CAUTION
Make sure that the original calculation of refrigerant is
correct. (e.g. take into account that due to additional
piping, additional refrigerant could be required).
Is the refrigerant circuit
charged correctly?
Yes
No
EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1
+ EK(2)CB07CAV3 + EKMBUHCA3V3+9W1
Action
Return to
"3.2.1 Checking
procedures" on page 92
of the
refrigerant circuit and continue
with the next procedure.
Open the stop valve of the
refrigerant circuit, see
"3.2.2 Repair procedures" on
page 93.
Then
Obstruction is possible.
Obstruction is less likely.
Action
Replace the clogged part, see
"3.2.2 Repair procedures" on
page 93.
Return to
"3.2.1 Checking
procedures" on page 92
of the
refrigerant circuit and continue
with the next procedure.
"3.2.2  Repair
Action
Return to
"3.2.1 Checking
procedures" on page 92
of the
refrigerant circuit and continue
with the next procedure.
Add or recuperate refrigerant
until correctly charged, see
"3.2.2 Repair procedures" on
page 93.
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02