baltur TBML 80 MC Instruction Manual For Installation, Use And Maintenance page 94

Progressive modulating two-stage mixed gas/diesel burner
Table of Contents

Advertisement

Available languages

Available languages

ENGLISH
irregularitY
The burner goes into lock-out
spraying liquid fuel but the flame does
not ignite. (red light on).
The burner goes into "lock-out", gas
flows, but there is no flame (red light
on).
Burner pump noisy.
poSSible cauSe
1
Pump pressure is not regular.
2
Water in the fuel.
3
Too much combustion air.
4
Air passage between flame disk and
diffuser excessively closed.
5
Nozzle worn out or dirty.
1
Air - gas ratio incorrect.
2
Gas pipe has not been properly bled of
air at the first ignition.
3
The gas pressure is insufficient or exces-
sive.
4
Air passage between flame disk and
diffuser too closed.
1
Pipe diameter too small.
2
Air infiltration in the pipes.
3
Dirty fuel filter.
4
Excessive distance and/or difference in
level between the tank and the burner or
numerous accidental leakages (elbows,
curves, bottlenecks, etc.)
5
Deteriorated flexible pipes.
42 / 50
0006160331_202310
remedY
1
Adjust.
2
Drain water from the tank using a suitable
pump. Never use the burner pump for this
purpose.
3
Reduce combustion air.
4
Correct the position of the combustion head
adjusting device.
5
Clean or replace.
1
Correct the air - gas ratio.
2
Bleed the gas pipe again, with due caution.
3
Check the maximum gas pressure value at
the time of ignition (use a water pressure
gauge, if possible).
4
Adjust the flame disk - diffuser.
1
Replace it according to the instructions.
2
Check and eliminate infiltrations.
3
Remove and wash.
4
Adjust the length of the suction pipe to
reduce the distance.
5
Replace.

Advertisement