am adjuStment of SerVomotor
1
On/Off lever for motor-camshaft coupling
2
Reference scale
3
Camshaft
4
Adjustable camshaft
I
Maximum air opening (130°)
II
Air regulation cam for gas minimum (30°) (<IV)
III
Air regulation cam for diesel minimum (90°) (>V)
IV
Gas ignition air opening (40°)
V
Diesel ignition air opening (80°)
VI
2nd diesel flame valve control cam (110°)
To modify the adjustment of the cams operate the respective
screws.The pointer on the red ring indicates the rotation angle set
for each cam on the respective reference scale.
34 / 50
0006160331_202310
SQm 40...
3
1
2
30
30
30
60
60
60
90
90
90
135
135
135
I
II
III IV
V
VI
4