Now the equipment is activated again and will automatically
switch to the second stage according to the program set by the
programmer.
Start the fuel supply auxiliary circuit and check for its correct
operation, then set pressure to nearly 0,5÷3 bar if such circuit
features a pressure regulator.
With the burner operating in the 2nd stage, adjust the quality of
air necessary to ensure efficient combustion.
Adjust the combustion so as to obtain a soft light orange flame;
avoid red flames with smoke and white flames with an excess of
air.
DANGER / ATTENTION
The burner must not operate below the stated minimum
capacity, in order to prevent damages to the combustion head
components.
During burner ignition, when it passes to the first stage, the air/
gas servomotor takes for a few seconds the burner to a delivery
higher than the first stage.
During this transition phase check that the cam (IV) for actuating
the servomotor second stage does not activate.