Control configuration (Password 241)

Input configuration

Internal inputs 1T temperature and 1H humidity (with added AES1-HT-A2, -A3 or -A5 element)
Parameter
Description
1T 00
1H 00
Enable internal sensor
1T 01
1H 01
Display minimum value
1T 02
1H 02
Display maximum value
1T 03
1H 03
Sensor sampling rate (control speed decrease as rate increases)
1T 04
1H 04
Sensor calibration
1T 05
1H 05
Alarm 1 low limit (1T), Alarm 3 low limit (1H)
1T 06
1H 06
Alarm 1/3 low limit values
1T 07
1H 07
Alarm 2 high limit (1T), Alarm 4 high limit (1H)
1T 08
1H 08
Alarm 2/4 high limit values
1T 09
1H 09
Hysteresis Alarm 1, 2, 3, 4
Calculate a range of inputs (0= not active):
1T 10
1H 10
1= average, 2= minimum, 3= maximum, 4= differential
Universal inputs 1U, 2U (TCI-W11-U: 1U only, TCI-W22-U: 1U and 2U)
Signal type (0= not active):
1U 00
1= 0-10V or 0-20mA, 2= 2-10V or 4-20mA, 3= passive temperature
1U 01
Display minimum value
1U 02
Display maximum value
1U 03
Analog input display range: 0= x 0.1, 1= x 1, 2= x 10, 3 = x 100
1U 04
Analog input unit of measure: 0= no unit, 1= %, 2= °C /°F, 3= Pa
1U 05
Sensor sampling rate (control speed decrease as rate increases)
1U 06
Sensor calibration
1U 07
Alarm 5 low limit (1U), Alarm 7 low limit (2U)
1U 08
Alarm 5/7 low limit value
1U 09
Alarm 6 high limit (1U), Alarm 8 high limit (2U)
1U 10
Alarm 6/8 high limit value
1U 11
Hysteresis alarm 5 and 6 (7 and 8)
Calculate a range of inputs (0=not active):
1U 12
1= average, 2= minimum, 3= maximum, 4= differential
Set jumpers on the back of the controller: 0–10VDC (default), 0–20mA, or RT/DI (passive temperature or binary)
Further define analog inputs with U00
Match sensor range to input display. With a differential pressure transmitter having 0–200 Pa measuring range set
UO1 display minimum to 0 and U02 display maximum to 200. The allowable range value of -50–205 may be adjusted
with multipliers inU03. The largest displayable values are -990–9999. Limiting range increases resolution.Applies to
analog as well as passive temperature inputs.
For binary input (open/close contact) set the jumper to RT/DI and parameter U00 to an analog input. An open
contact reads as a high value (100%), a closed contact as a low value (0%).
Enable / Disable an alarm. Setting the alarm enable to OFF will prevent the alarm from being displayed on screen. It
may never the less be used to control an output by setting the appropriate output alarm flags. This way, an alarm
limit may be used as interlock.
Specify the input value that triggers an alarm. Hysteresis is the difference between alarm level input and value
required to turn the alarm off. An alarm is displayed as text if enabled (see table). Alarm text can be set to blink
continuously until acknowledged by pressing the OPTION button or only while the alarm conditions are active (see
user parameter UP15).
Input
Low limit
High limit
Calculate mathematical functions over multiple inputs for loop control or display with xU12. In order to calculate
average, minimum or maximum between several inputs, make sure all the inputs are of identical type and range and
then activate the same function on xU12 on all the selected inputs. The largest input of the group selected will carry
the calculated value.For example: When average is activated on 2U12 and 1U12 = 1, the average is carried on
UI2.UI2 may now be used as input for control loops and it will show the average value of UI1 and UI2 combined. It is
possible to use different functions on different inputs. For example: minimum of UI1 and UI3 and maximum of UI2
and UI4.
The differential function may only be calculated on subsequent inputs. Such as UI2-UI1. The function must only be
activated on the minuend (UI2 in this example). The displayed value of the minuend will change into the difference:
UI2 in – UI1 = UI2 out. It is possible to have multiple differentials on one controller. It is not possible to reverse the
subtraction to UI1-UI2.
Doc: 70-00-0158, V1.1, Date: 20160621
Subject to alteration
1T
1H
ALA1
ALA3
ALA2
ALA4
© Vector Controls GmbH, Switzerland
TCI-W Universal Controller
I
C
NPUT
ONFIGURATION
Range
OFF/ON
-50–205
-50–205
0–100
per input
OFF/ON
-40–215°C
OFF/ON
-40–215°C
50°C / 95%
0–100°
0–3
0–3
-50–205
-50–205
0–3
0–3
0–100
Per input
OFF/ON
-40–215°C
OFF/ON
-40–215°C
50°C(122°F)
0–100°
0–4
1U
2U
ALA5
ALA7
ALA6
ALA8
Default
ON
0
100
10
0
OFF
5°C/5%
OFF
5°C/5%
0
1
0
100
1
2
10
0
OFF
5°C(41°F)
OFF
5°C(10°F)
0
Page 8