Setting parametersto configurethe controller
TCI is an intelligentcontroller with the flexibility to fit a wide range of applications. The control operation is defined by
parameters set using the standard operation terminal. There are two levels:
1.
User/display parameters (password 0009)
2.
Control parameters (password 00241)
Recommended set-up procedure:
1.
Set jumpers on the back of the controller for inputs and outputs
2.
Connect power supply and inputs
3.
Make sure Celsius – Fahrenheit settings are correct (UP07)
4.
Program input parameters
5.
Program control parameters
6.
Program output parameters
7.
Program auxiliary functions and user settings
8.
Test function of unit
9.
Switch off power
10. Connect outputs
11. Test control loop
Parameters are grouped according to modules:
Module
Description
UP
User and display parameters
UI
Input configuration: 1T, 1H, 1U, 2U
LP
Control loops Lp1, Lp2
AO
Analog output configuration, AO1
DO
Binary output configuration, do1, do2
FU
Special functions
How to change parameters
1.
Press UP/DOWN buttons simultaneously for three seconds. The display will show firmware version and revision
number. Press the OPTION button to start login.
2.
CODE is shown in small display.
3.
Code to access user parameters is 009, control parameter is 241. The access numbers are fixed and cannot be
changed.
4.
Select this using UP/DOWN buttons.
5.
Press OPTION after selecting the correct code.
6.
Once logged in with 009, the user/display parameters are displayed immediately. Once logged in with 241 control
modules are displayed (Lp1, Lp2, 1u, 2u, etc.) –select with UP/DOWN and open with OPTION. As soon as the module
is open its parameters are displayed.
7.
Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION button. Three arrows
are displayed to indicate that the parameter may be modified. Use UP/DOWN buttons to adjust the value.
8.
After you are done, press OPTION to save the new value and return to the selection level (arrows disappear when
selection is saved). Pressing left hand POWER button without pressing OPTION will discard the value and return
without saving. For control parameters press POWER again to leave parameter selection and return to control module
selection.
9.
Press the POWER to leave the menu. The unit will return to normal operation if no button is pressed for more than 5
minutes.
Doc: 70-00-0158, V1.1, Date: 20160621
Subject to alteration
Notes
Control user access and select display elements,
regional settings
TCI-W22: Internal temp. and RH, 2 universal inputs
TCI-W11: Internal temp. 1 universal input
TCI-W22: 2 independent control loops
TCI-W11: 1 independent control loop
TCI-W11 and TCI-W22 : 1 analog output
TCI-W11 and TCI-W22: 2 binary (digital) outputs -
relays
Common to all TCI
© Vector Controls GmbH, Switzerland
TCI-W Universal Controller
S
C
ETUP AND
ONFIGURATION
PW
009
241
Page 6