Input Configuration - Vector 40-10 0259 Manual

Wall mounted universal controller
Table of Contents

Advertisement

Control configuration (Password 241)

Input configuration

Internal inputs 1T temperature and 1H humidity (with added AES3-HT-A2, -A3 or -A5 element)
Parameter
Description
1T 00
1H 00
Enable internal sensor
1T 01
1H 01
Display minimum value
1T 02
1H 02
Display maximum value
1T 03
1H 03
Sensor sampling rate (control speed decrease as rate increases)
1T 04
1H 04
Sensor calibration
1T 05
1H 05
Alarm 1 low limit (1T), Alarm 3 low limit (1H)
1T 06
1H 06
Alarm 1 (1T), Alarm 3 (1H) low limit values
1T 07
1H 07
Alarm 2 (1T), Alarm 4 (1H) high limit
1T 08
1H 08
Alarm 2 (1T), Alarm 4 (1H) high limit values
1T 09
1H 09
Hysteresis Alarm 1, 2 (1T), 3, 4 (1H)
Calculate a range of inputs (0= not active):
1T 10
1H 10
1= average, 2= minimum, 3= maximum, 4= differential
Universal inputs 1U = UI1, external passive input 2T = TI2 (TCI-W23 only)
Signal type (0= not active):
1U 00
2T 00
1= 0-10V or 0-20mA, 2= 2-10V or 4-20mA, 3= passive temperature
1U 01
2T 01
Display minimum value
1U 02
2T 02
Display maximum value
1U 03
2T 03
Analog input display range: 0= x 0.1, 1= x 1, 2= x 10, 3 = x 100
1U 04
2T 04
Analog input unit of measure: 0= no unit, 1= %, 2= °C /°F, 3= Pa
1U 05
2T 05
Sensor sampling rate (control speed decrease as rate increases)
1U 06
2T 06
Sensor calibration
1U 07
2T 07
Alarm 5 (1U), Alarm 7 (2T) low limit
1U 08
2T 08
Alarm 5 (1U), Alarm7 (2T) low limit value
1U 09
2T 09
Alarm 6 (1U), Alarm 8 (2T) high limit
1U 10
2T 10
Alarm 6 (1U), Alarm 8 (2T) high limit value
1U 11
2T 11
Hysteresis alarm 5 and 6 (1U), alarm 7 and 8 (2T)
Calculate a range of inputs (0=not active):
1U 12
2T 12
1= average, 2= minimum, 3= maximum, 4= differential
Set jumpers on the back of the controller: 0–10VDC (default), 0–20mA, or RT/DI (passive temperature or binary)
Further define analog inputs with U00
Match sensor range to input display. With a differential pressure transmitter having 0–200 Pa measuring range set
UO1 display minimum to 0 and U02 display maximum to 200. The allowable range value of -50–205 may be adjusted
with multipliers inU03. The largest displayable values are -990–9999. Limiting range increases resolution. Applies to
analog as well as passive temperature inputs.
For binary input (open/close contact) set the jumper to RT/DI and parameter U00 to an analog input. An open
contact reads as a high value (100%), a closed contact as a low value (0%).
Enable / Disable an alarm. Setting the alarm enable to OFF will prevent the alarm from being displayed on screen. It
may never the less be used to control an output by setting the appropriate output alarm flags. This way, an alarm
limit may be used as interlock.
Specify the input value that triggers an alarm. Hysteresis is the difference between alarm level input and value
required to turn the alarm off. An alarm is displayed as text if enabled (see table). Alarm text can be set to blink
continuously until acknowledged by pressing the OPTION button or only while the alarm conditions are active (see
user parameter UP15).
Input
Low limit
High limit
Calculate mathematical functions over multiple inputs for loop control or display with xU12. In order to calculate
average, minimum or maximum between several inputs, make sure all the inputs are of identical type and range and
then activate the same function on xU12 on all the selected inputs. The largest input of the group selected will carry
the calculated value. For example: When average is activated on 2T12 and 1U12 = 1, the average is carried on UI2.
UI2 may now be used as input for control loops and it will show the average value of UI1 and TI2 combined. It is
possible to use different functions on different inputs. For example: minimum of UI1 and UI3 and maximum of UI2
and UI4.
The differential function may only be calculated on subsequent inputs. Such as TI2-UI1. The function must only be
activated on the minuend (TI2 in this example). The displayed value of the minuend will change into the difference:
TI2 in – UI1 = TI2 out. It is possible to have multiple differentials on one controller. It is not possible to reverse the
subtraction to UI1-TI2.
Doc: 70-00-0365C, V2.0, 20220523
Subject to alteration
1T
1H
ALA1
ALA3
ALA2
ALA4
© Vector Controls GmbH, Switzerland
TCI-W13, TCI-W23 Universal Controller
I
NPUT
1U
ALA5
ALA6
C
ONFIGURATION
Range
Default
OFF/ON
ON
-50–205
0
-50–205
100
0–100
10
per input
0
OFF/ON
OFF
-40–215°C
5°C/5%
OFF/ON
OFF
-40–215°C
50°C / 95%
0–100°
5°C/5%
0–3
0
0–3
1
-50–205
0
-50–205
100
0–3
1
0–3
2
0–100
10
Per input
0
OFF/ON
OFF
-40–215°C
5°C(41°F)
OFF/ON
OFF
-40–215°C
50°C(122°F)
0–100°
5°C(10°F)
0–4
0
2T
ALA7
ALA8
Page 11-22

Advertisement

Table of Contents
loading

Table of Contents