Enable/disable
Parameter
Description
Fu 12
Select enable–disable input (0=function disabled):
1= 1T, 2= 1H, 3= 1U, 4= 2U
FU 13
Manual override permitted (without waiting for delay). This function
allows starting the controller, even the enable conditions are not met.
The controller will switch off again if the running conditions are not met
until the disable delay is expired.
Fu 14
Enable delay (seconds)
Fu 15
Disable delay (seconds)
Range of limits:
Fu 16
OFF = When limit 2 is greater thanlimit 1, enable when input value is
greater than limit 2,disable when input value is less thanlimit 1. When
limit 2 is less thanlimit 1, enable when input value less than limit 1,
disable when input value is greater thanlimit 2.
ON = When limit 2 is greater thanlimit 1enable when input value is
between limit 1 andlimit 2. When limit 2 is less thanlimit 1, enable
when input value below limit 2 or above limit 1
Fu 17
Input limit 1
Fu 18
Input limit 2
Fu 19
Disable in case of alarms
Enable or disable the controller based on desired input values, such as high or low temperature, occupancy sensor,
window contact, etc. Can be used as and function where several conditions must be met before disable or enable.
Time schedules do not override, but manual override is permitted. Delay times may be assigned for both enable and
disable (allows for the controller to start before validation of operation values takes place). Set input limit 1 and 2
with options below. Example: With FU16=OFF, and Limit 2 > Limit 1, switch enable-to-disable at Limit 1, disable-to-
enable at Limit 2.
Mode
Mode
Doc: 70-00-0158, V1.1, Date: 20160621
Subject to alteration
Limit 2 > Limit 1
Enable
Disable
Limit
Limit
Input
1
2
Enable
Disable
Limit
Limit
Input
1
2
© Vector Controls GmbH, Switzerland
TCI-W Universal Controller
A
F
UX
UNCTIONS
Range
ON/OFF
0–1275s
0–1275s
ON/OFF
per input
Per input
Selection
Limit 1 > Limit 2
Enable
Mode
Disable
Limit
2
Mode
Limit
Limit
2
1
C
ONFIGURATION
Default
0–4
0
OFF
0
300
OFF
10
90

Limit
Input
1
Enable
Disable
Input
Page 16