TCI-W13, TCI-W23 Series wall mounted universal controller
Applications
Fan coil units
Heat exchangers
Zoning
General
TCI-W13: 1 independent control loop, 1 internal temperature sensor, 1 universal input (analog/binary/temp),
1 binary output, 2 analog outputs
TCI-W23: 2 independent control loops, 1 internal temperature sensor, 1 universal input, 1 passive input,
1 binary output, 2 analog outputs.
Internal temperature sensor standard. Add replaceable humidity element as required or order -H version:
AES3-HT-A2 (2%), AES3-HT-A3 (3%) or AES3-HT-A5 (5%)
Flexible application configuration is made with a parameter-setting routine using the standard operation terminal
Name
- W
T
C
I
2
Ordering
Model
Item code
TCI-W13
40-10 0170
TCI-W13-H
40-10 0171
TCI-W23
40-10 0172
TCI-W23-H
40-10 0173
AES3-HT-A2
40-50 0102
AES3-HT-A3
40-50 0103
AES3-HT-A5
40-50 0104
Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy: SDB-Tn10-20 (duct), SRA-Tn10
(room), SDB-Tn10-20 + AMI-S10 as immersion sensor.
Actuators: Choose modulating actuators with an input signal type of 0...10 V DC or 4...20 mA (min. and max. signal
limitations may be set with parameters. 3-point point actuators with constant running time are recommended).
Binary auxiliary devices (e.g. pumps, fans, on/off valves, humidifiers, etc.): Do not directly connect devices that
exceed specified limits in technical specifications – observe startup current on inductive loads.
Doc: 70-00-0365, V1.0, 20200304
Subject to alteration
VAV
Air handlers
Fan, pump control
-
3
U
Housing
In/Outputs:
Control loops:
Mounting:
Series:
Temperature
Loop
input
1
1
2
TCI-W13, TCI-W23 Universal Controller
Features
Universal PI and/or binary control for any analog
input/output signal and range
Multiple auxiliary functions: heat-cool auto changeover,
automatic enable, set point compensation
Differential, averaging, min and max functions
Cascading of control loops (-W23 type)
Alarm monitoring of low and high limits on all inputs
Programmable reaction in case of alarm
Feedback function for inputs and set points
Functions for dehumidifying, set point shift, cascade control
Password protected programmable user and control
parameters
TCI-W23 also includes
Power cap protected real-time clock with 48 hr power backup
7-day programmable schedules, with options including
change of set points and direct position of manual outputs
Blue backlight
Humidifiers
Dehumidifiers
Ventilation
Blank = square housing
See table below
1 = 1 control loop, 2 = 2 control loops
W = Wall mounted
TCI
Humidity
UI
TI
input
0
1
0
1
0
1
1
1
1
1
1
© Vector Controls GmbH, Switzerland
O
Radiant heating
Radiant cooling
Pressurization
Binary
Analog
output
output
RH sensor 3% acc.
1
2
7-day programmable
RH sensor 3% acc.
RH sensor 2% acc.
RH sensor 3% acc.
RH sensor 5% acc.
VERVIEW
Option
Standard
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for Vector TCI-W13-H

  • Page 1 40-50 0104 RH sensor 5% acc. Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy: SDB-Tn10-20 (duct), SRA-Tn10 (room), SDB-Tn10-20 + AMI-S10 as immersion sensor. Actuators: Choose modulating actuators with an input signal type of 0…10 V DC or 4…20 mA (min. and max. signal limitations may be set with parameters.
  • Page 2: Technical Specifications

    Power case: ø 58 x 32 mm (ø 2.3” x 1.3”) RoHS compliant according to 2011/65/EU Weight (including package) TCI-W13 = 253 g (8.9 oz), TCI-W23 = 262 g (9.3 oz) Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 2 Subject to alteration...
  • Page 3: Terminal Description

    TCI is designed for operation of 24 VAC safety extra-low voltage and is short-circuit-proof. Supplying voltages above 24 VAC to low voltage connections may damage the controller or other devices. Connection to voltages exceeding 42 V endangers personnel safety. Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 3 Subject to alteration...
  • Page 4: Display And Operation

    Verify input connections, jumper settings and parameter settings for the input involved Err3: A function refers to a disabled input. Disable the function or enable the input Err4: Internal failure. Product must be replaced Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 4 Subject to alteration...
  • Page 5 Available actions blink as you scroll through them, Press OPTION to select one: Pr01 Characteristics of action (e.g. 0…100% for A1) appear (4 bar indicates step 4 complete) 08:00 Press UP/DOWN to select, OPTION to complete Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 5 Subject to alteration...
  • Page 6 For control parameters press POWER again to leave parameter selection and return to control module selection Press the POWER to leave the menu. The unit will return to normal operation if no button is pressed for more than 5 minutes Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 6 Subject to alteration...
  • Page 7 1...255 = Delay for controller to go back to the scheduled Energy Hold OFF, 60 min (TCI-W23) ECONOMY, or COMFORT operation mode if the operation mode is changed manually. Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 7 Subject to alteration...
  • Page 8: Input Configuration

    TI2 in – UI1 = TI2 out. It is possible to have multiple differentials on one controller. It is not possible to reverse the subtraction to UI1-TI2. Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 8 Subject to alteration...
  • Page 9: Control Loop Configuration

    Commonly this is used for humidity control to avoid condensation on outside walls or windows in very cold weather. Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 9 Subject to alteration...
  • Page 10 Dead zone h/c set points Economy mode set point shift Set point heating/reverse Set point cooling/direct T [°C, °F] PI sequence heating/reverse U [V, mA] PI sequence cooling/direct Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 10 Subject to alteration...
  • Page 11 Offset cooling/reverse Dead zone Economy set point shift Set point heating/reverse Set point cooling/direct T [°C, °F] U [V, mA] Binary sequences cooling/direct Binary sequences heating/reverse Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 11 Subject to alteration...
  • Page 12: Output Configuration

    1A03. As the system moves into heating mode, heating airflow increases until it reaches the maximum heating output (1A04), typically 30 to 50% of maximum cooling airflow. Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 12 Subject to alteration...
  • Page 13 100 seconds as the lifetime of the relays will be shortened with frequent switching. For PWM applications requiring cycle times below 100 seconds we recommend using TCY-FT with TRIAC outputs. Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 13 Subject to alteration...
  • Page 14: Auxiliary Functions

    Activate comfort/economy changeover with loop configuration parameter (L07). Limit 2 > Limit 1 Limit 1 > Limit 2 Comfort Comfort Mode Mode Standby Standby Limit Limit Limit Limit Input Input Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 14 Subject to alteration...
  • Page 15: Aux Functions

    Limit 1 > Limit 2 Enable Enable Mode Mode Disable Disable Limit Limit Limit Limit Input Input Enable Mode Mode Enable Disable Disable Limit Limit Limit Limit Input Input Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 15 Subject to alteration...
  • Page 16 Limit 1, cool to heat at Limit 2. For binary open/close contact, open is a high value (100%), closed is a low value (0%). Limit 2 > Limit 1 Limit 1 > Limit 2 Heat Heat Mode Mode Cool Cool Limit Limit Limit Limit Input Input Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 16 Subject to alteration...
  • Page 17 TCI-W-U Universal Controller Smart Sensors and Controls Made Easy! Quality - Innovation – Partnership Vector Controls GmbH Switzerland info@vectorcontrols.com www.vectorcontrols.com Doc: 70-00-0365, V1.0, 20200304 © Vector Controls GmbH, Switzerland Page 17 Subject to alteration...

Table of Contents