TCI-W13, TCI-W23 Series wall mounted universal controller
Applications
•
Fan coil units
•
Heat exchangers
•
Zoning
General
•
TCI-W13: 1 independent control loop, 1 internal temperature sensor, 1 universal input (analog/binary/temp),
1 binary output, 2 analog outputs
•
TCI-W23: 2 independent control loops, 1 internal temperature sensor, 1 universal input, 1 passive input,
1 binary output, 2 analog outputs.
•
Internal temperature sensor standard. Add replaceable humidity element as required or order -H version:
AES3-HT-A2 (2%), AES3-HT-A3 (3%) or AES3-HT-A5 (5%)
•
Flexible application configuration is made with a parameter-setting routine using the standard operation terminal
Name
- W
T
C
I
2
Ordering
Model
Item code
TCI-W13
40-10 0170
TCI-W13-H
40-10 0171
TCI-W23
40-10 0172
TCI-W23-H
40-10 0173
AES3-HT-A2
40-50 0102
AES3-HT-A3
40-50 0103
AES3-HT-A5
40-50 0104
Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy: SDB-Tn10-20 (duct), SRA-Tn10
(room), SDB-Tn10-20 + AMI-S10 as immersion sensor.
Actuators: Choose modulating actuators with an input signal type of 0...10 V DC or 4...20 mA (min. and max. signal
limitations may be set with parameters. 3-point point actuators with constant running time are recommended).
Binary auxiliary devices (e.g. pumps, fans, on/off valves, humidifiers, etc.): Do not directly connect devices that
exceed specified limits in technical specifications – observe startup current on inductive loads.
Doc: 70-00-0365, V1.0, 20200304
Subject to alteration
•
VAV
•
Air handlers
•
Fan, pump control
-
3
U
Housing
In/Outputs:
Control loops:
Mounting:
Series:
Temperature
Loop
input
1
1
2
TCI-W13, TCI-W23 Universal Controller
Features
•
Universal PI and/or binary control for any analog
input/output signal and range
•
Multiple auxiliary functions: heat-cool auto changeover,
automatic enable, set point compensation
•
Differential, averaging, min and max functions
•
Cascading of control loops (-W23 type)
•
Alarm monitoring of low and high limits on all inputs
•
Programmable reaction in case of alarm
•
Feedback function for inputs and set points
•
Functions for dehumidifying, set point shift, cascade control
•
Password protected programmable user and control
parameters
TCI-W23 also includes
•
Power cap protected real-time clock with 48 hr power backup
•
7-day programmable schedules, with options including
change of set points and direct position of manual outputs
•
Blue backlight
•
Humidifiers
•
Dehumidifiers
•
Ventilation
Blank = square housing
See table below
1 = 1 control loop, 2 = 2 control loops
W = Wall mounted
TCI
Humidity
UI
TI
input
0
1
0
1
0
1
1
1
1
1
1
© Vector Controls GmbH, Switzerland
O
•
Radiant heating
•
Radiant cooling
•
Pressurization
Binary
Analog
output
output
RH sensor 3% acc.
1
2
7-day programmable
RH sensor 3% acc.
RH sensor 2% acc.
RH sensor 3% acc.
RH sensor 5% acc.
VERVIEW
Option
Standard
Page 1