Dimensions, mm(inch)
88 (3.5)
Connection
0-48VAC, 0-30VDC
24V AC/DC
2
G
1
G0
0V (COM)
0V AC
0-48VAC, 0-30VDC
24V AC/DC
2
G
1
G0
0V (COM)
0V AC
Terminal Description
G0
Power supply:
G
Power supply:
Q..
Binary outputs:
X
Universal input:
U1, u2
Ym1
Analog output:
X
Internal temperature input
T1
X
Internal humidity input if AES1-HT is inserted
H1
Use copper, twisted pair, conductors only. The operating voltage must comply with the requirements for safety extra-low
voltage (SELV) as per EN 60 730. Use safety insulating transformers class II with double insulation as per EN 60 742;
they must be designed for 100% ON-time. When using several transformers in one system, the connection terminal 1
must be galvanic connected. TCI is designed for operation of AC 24 V safety extra-low voltage and is short-circuit-proof.
Supplying voltages above AC 24 V to low voltage connections may damage the controller or other devices. Connection to
voltages exceeding 42 V endangers personnel safety.
Doc: 70-00-0158, V1.1, Date: 20160621
Subject to alteration
32 (1.2)
X
U1
3
1
7
Q13
G0
X1
4
5
Q14
Q24
Y
Y
B1
B2
X
U1
3
1
7
Q13
G0X1
4
5
Q14
Q24
Y
Y
B2
B1
0V, -24VDC; common for power supply, analog in- and outputs
24VAC, +24VDC
Potential free relays contacts (see technical specification)
Yb1,b2
Binary output common
NTC 10kΩ @ 25°C (77°F), 0...10 V or 0...20 mA(selectable by jumper)
0...10 V or 0...20 mA
© Vector Controls GmbH, Switzerland
TCI-W Universal Controller
Installation
21
(0.8)
Install the controller on an easy accessible
interior wall, approx. 1.5 m above the floor
in an area of average temperature.
Avoid direct sunlight or other heat sources,
e.g. the area above radiators and heat
emitting equipment.
Avoid locations behind doors, outside walls
and below or above air discharge grills and
diffusers.
Location of mounting is less critical if
external temperature sensors are used.
Ensure adequate air circulation to dissipate
heat generated during operation.
Observe local regulations.
Do not mount in a wet or condensation
prone environments.
X
U2
1
8
X
G0X2
T1
16
G0Y1
Y
M1
X
T1
1
6
G0
Y1
Y
M1
*
O
PERATION
Warning:
Live Electrical
Components!
X
During installation,
H1
testing, servicing and
troubleshooting of
TCI-W22
Vector Controls
products, it may be
necessary to work with
live electrical
components. Have a
qualified licensed
electrician or other
individual who has been
properly trained in
handling live electrical
components perform
these tasks. Failure to
follow all electrical
safety precautions
X
when exposed to live
H1
electrical components
TCI-W11
could result in death or
serious injury.
Page 3