Faults
7.2 Service technician faults
Message frame text Backend ⇒ Charging station: Faulted
Component: Charging point 1 or 2
Status LED: Flashes red 2x
Description
Main contactor fault
Circuit breaker fault
Message frame text Charging station ⇒ Backend: OverCurrentFailure
Message frame text Backend ⇒ Charging station: Faulted
Component: Charging point 1 or 2
Status LED: Flashes red 3x
Description
•
Circuit breaker error
•
Circuit breaker has tripped
Overcurrent detected
RCCB fault
Message frame text Charging station ⇒ Backend: GroundFailure
Message frame text Backend ⇒ Charging station: Faulted
Component: Charging point 1 or 2
Status LED: Flashes red 4x
Description
Ground fault detected
78
Cause
The main contactor gets stuck.
Auxiliary contact faulty
Wrong type of contactor
Cause
The main contactor gets stuck. The EVSE-
controller triggers the circuit breaker for
safety reasons.
Loose connections on the auxiliary con
tact wiring.
Circuit breaker defective
Circuit breaker has tripped.
Circuit breaker trips again after reset
(< 2 s).
Cause
RCCB has tripped.
The RCCB tripped when the charging
started.
Solution
Replace the main contactor.
Check the auxiliary contact.
Replace the auxiliary contact if neces
sary.
Check whether the correct type of con
tactor is installed. For example, a DC con
tactor has been replaced by an AC con
tactor.
Solution
Replace the main contactor.
Check the wiring between the main con
tactor auxiliary contact and the EVSE-
controller.
Tighten the terminal points.
Check the circuit breaker. Replace the cir
cuit breaker if necessary.
Check the circuit breaker and reset it.
See row: Circuit breaker error
Solution
Check the RCCB.
Switch the RCCB on again.
Make sure that all cables have the cor
rect voltage.
SICHARGE Operating Instructions MID
Operating Instructions, 02/2023, A5E48573001-AF