Connection to a PC by Host Link via RS-422A
S CPU-mounting Host Link Units: C120-LK201-V1 and C120-LK202-V1
Setting the Rear Switches
S Unit #, parity, and transfer code (DIP switch SW1 pins
1 to 5)
Set pins 1 to 5 to OFF (0).
* Parity is fixed at even parity. Transfer code is fixed
at ASCII 7 data bits and 2 stop bits.
S Baud rate (DIP switch SW2 pins 1 to 4)
Set these pins to 1010 to select 9,600 bps.
Set these pins to 0010 to select 19,200 bps.
S 1-to-1/1-to-N selection (DIP switch SW2 pin 6)
Set pin 6 to OFF (0) (1-to-N).
S Command level (C120-LK201-V1) (DIP switch SW2 pins 7 and 8)
Set these pins to ON (1).
(Levels 1, 2, and 3 are enabled.)
S CTS selection (C120-LK201-V1)
(DIP switch SW3 pins 1 and 2)
Set pin 1 to ON (1) and pin 2 to OFF (0).
(Set this always to 0 V.)
S Synchronization (C120-LK201-V1)
(DIP switch SW3 pins 3 to 6)
Set pins 3 and 5 to ON (1) and pins 4 and 6 to OFF (0).
Set this to Internal synchronization.
S Terminator setting (C120-LK202-V1)
(DIP switch SW3 pins 1 to 6)
When using an RS-422A cable, set pins 1, 3, and 5 to ON (1), and
set pins 2, 4, and 6 to OFF (0).
(Set this for termination.)
Note: Set the Link Adapter for termination too.
S CVM1/CV-series Rack-mounting Host Link Unit: CV500-LK201
Setting the Front Switches
Set the operating conditions with the CPU Bus Unit setting functions when an
NT30/30C and a CVM1/CV-series Host Link Unit is connected to the NT30/30C.
The CPU Bus Unit setting can be made directly from the Programming Device
(CX-Programmer) or the CPU Bus Unit setting information created with a Pro-
gramming Device can be transferred to the CPU Unit.
Section
(0: OFF, 1: ON)
2-6
51