FIELD INSTALLED UPM INSTALLATION PLAN AND UNPACKING
3−2
EATON 9395 Field Installed UPM Mechanical Installation Manual
The FI−UPM operating environment must meet the weight requirements shown in
Table 3-1 and the size requirements shown in Figure 3-1 through Figure 3-6.
Dimensions are in millimeters (inches).
Table 3-1. FI−UPM Cabinet Weight
Model
Eaton 9395 FI−UPM
The FI−UPM cabinet uses forced air cooling to regulate internal component
temperature. Air inlets are in the front of the cabinet and outlets are in the top. Allow
clearance in front of and above each cabinet for proper air circulation. The clearances
required around the FI−UPM cabinet are shown in Table 3-2.
Table 3-2. FI−UPM Cabinet Clearances
From Top of Cabinet
457.2 mm (18") minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36") working space
From Back of Cabinet
None Required
From Right Side of Cabinet None Required
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the FI−UPM are:
S
Ambient Temperature Range:
S
Recommended Operating Range: 20–25°C (68–77°F)
S
Maximum Relative Humidity:
The FI−UPM ventilation requirements are shown in Table 3-3.
Table 3-3. FI−UPM Air Conditioning or Ventilation Requirements During Full Load Operation
Rating
Input/Output Voltage
400/400
225 kVA
480/480
400/400
275 kVA
480/480
400/400
300 kVA
480/480
S
Shipping
642 (1415.4)
0–40°C (32–104°F)
95%, noncondensing
Heat Rejection
BTU/hr  1000 (kg−cal/hr)
43 (10943)
44 (11054)
53 (13375)
54 (13510)
51 (12969)
51 (12969)
164201717 Rev 3 www.eaton.com/powerquality
Weight
kg (lb)
Installed
606 (1336)
Ventilation Required for
Cooling Air Exhaust
Approximately
755 liter/sec
(1600 cfm)