9.2.2
Control line connection
Pendant with cable and plug-in connection. Plug-in before use.
Any changes of the power supply cable must only be effected by qualified personnel.
9.2.3
Power connection of the brake
The low-maintenance D.C. spring-pressure brakes are connected at the factory according to the wiring
diagram.
NOTICE!
The power supply cable must be equipped by the customer with slow-blow fuses and mains connection
switch.
CAUTION!
Precondition for actuation of the overload protection is the correct winding direction of the wire rope!
This may be mixed up for winches with three phase current motor.
The symbols on the control switch than do not match to the wiring direction of the wire rope.
In this case, the winch must be stopped immediately.
Exchange two phases of the main current supply.
Test the winding direction of the wire rope.
9.2.4
Wiring diagram
Wiring diagrams are situated in the terminal box or can be requested from HADEF by metioning of serial
number.
9.2.5
Assignment recommendation of line cross-sections and fuses
Assignment of line cross-sections and fuses must be done acc. to VDE0100.
For total motor output add all motor output data. The technical data of the motors are found in chapter
„Technical Data" resp.on the motor name plates.
Motor output
Fuse
up to
Slow-blow
kW
A
1,1
10
2,2
16
4
20
5,5
35
12
50
NOTICE!
The values listed in the table refer to 400V/50 Hz three-phase current and are recommendations.
The exact determination of the supply line must be carried out on site by a specialist.
9.3

Gear

NOTICE!
For transport, some gear types are fitted with a plug screw. Replace the plug screw by a ventilation screw
(attached) before putting the unit into operation.
9.4

Wire rope

Wire ropes must be free from corrosion, dirt or damage.
They must be lubricated before commissioning.
No lubrication shortens the lifetime of the wire rope and the maintenance intervals.
WARNING!
It is not allowed to use plastic wire ropes or plastic-coated wire ropes.
18
Start up-/
Line cross section (mm²) for line length L (m)
Nominal current
Ia / In
L < 50
1,5
3-7- times
2,5
4
6
50 < L < 100
100 < L < 150
2,5
4
6
4
10
10
5.52.262.00.01.13