Cable cross-section 5.5-8.0 mm
7 mm
Fig. 47. Wire end stripping.
Use a flat head screwdriver to open the retaining bracket on
3.
the connector, as shown in Fig. 48.
Fig. 48. Opening the retaining bracket.
Insert the stripped DC cable far enough into the battery con-
4.
nector and replace the retaining bracket to make sure it is
locked tightly to the stripped cable, as shown in Fig. 49.
Fig. 49. Inserting the DC cable into the battery connector.
Push the battery connector up to the threaded joint and use an
5.
open-end spanner to firmly lock the connector with a torque of
2 Nm, as shown in Fig. 50.
Fig. 50. Locking the connector.
1. Before carrying out the connection, make sure
that the polarity of the cable is correct.
Warning
2. Use a multimeter to measure the voltage of
the battery pack and make sure that the voltage
is within the inverter limits and that the polarity
is correct.
Insert the positive and negative connectors into the respec-
6.
tive inverter battery terminals. When you hear a "click" it is
properly assembled
74
2
5.3.4.3. Steps for the connection of
The communications cable required for connection to the meter is
connected to the inverter at the factory. It is identified as "BMS".
If you have accidentally disconnected it or need to connect a longer
one, etc., unscrew the protective casing, pass it through the right
cable gland that is labelled BMS and connect it to the RJ45 port
labelled with the same name.
Fig. 52. Identification of the RJ45 port on the inverter.
Fig. 53. Connecting the inverter communications to the SALICRU
Fig. 51. Connecting the battery.
To connect the battery, optional equipment must be pur-
chased. See the manual for battery EL...
communications between
battery system and inverter.
battery system.
SALICRU