Adjustment (Calibration) Of The Frequency Meter (Indicator) - Mitsubishi Electric FR-S520E-0.1K Instruction Manual

Table of Contents

Advertisement

5.2 Adjustment (calibration) of the frequency meter (indicator)

Changing example
POINT
The calibration parameters "C1" can be made to be read by setting "1" (extended
function parameter valid) in Pr. 30 "extended function display selection".
Set the value of the calibration parameter C1 "FM terminal calibration".
Operation
PU operation mode
1. Press the
to choose the
MODE
parameter setting mode.
2. Turn the
to show "
setting.
Pr. 30 must be set to "1".
(For details, refer to steps
page 22
3 to 6 on
3. Press the
SET
"
".
Turn the
until the calibration
4.
parameter C1 "FM terminal
calibration" appears.
5. Press the
SET
6. If the inverter is at a stop,
press the
RUN
(A motor need not be connected.)
Turn the
to adjust the indicator
7.
needle to the desired position.
8. Press the
SET
Setting is complete.
·
By turning the
·
Press the
·
Press the
REMARKS
Depending on the set value, it may take some time for the needle to move.
If "1" is set in Pr. 30 "extended function display selection", the calibration parameter C1 "FM
terminal calibration" can also be set in the external operation mode.
POINT
By setting the Pr. 54 "FM terminal function selection" value, preset Pr. 55
"frequency monitoring reference" or Pr. 56 "current monitoring reference" to the
running frequency or current value at which the output signal is 1440 pulses/s.
At 1440 pulses/s, the meter generally deflects to full-scale.
Deflecting the meter (analog indicator) to full-scale (1mA) at the preset
frequency of 60Hz.
(Refer to page 19 for frequency setting.)
"
.)
to show
to enable setting.
to start the inverter.
.
, you can read another parameter.
SET
to return to the "
twice to show the next parameter (
SET
Adjustment (calibration) of the frequency meter (indicator)
Display
MODE
SET
SET
RUN
SET
Flicker...Parameter setting complete!!
" indication (step 3).
31
The parameter
number read
previously
appears.
RUN
PU
EXT
Analog indicator
).
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents