Adjustment Of The Frequency Setting Potentiometer And Indicator - Mitsubishi Electric FR-S520E-0.1K Instruction Manual

Table of Contents

Advertisement

5.
ADJUSTMENT OF THE FREQUENCY SETTING
POTENTIOMETER AND INDICATOR
Related parameters
Parameter
38
Frequency setting voltage gain frequency
39
Frequency setting current gain frequency
C2
Frequency setting voltage bias frequency
C3
Frequency setting voltage bias
C4
Frequency setting voltage gain
C5
Frequency setting current bias frequency
C6
Frequency setting current bias
C7
Frequency setting current gain
*1. Settings may differ because of calibration parameters.
60Hz
Factory setting
(
Pr.38
)
0Hz
(
C2
)
0V
C3
(0%
Frequency setting voltage signal
*2. Pr. 73 "0-5V/0-10V selection" changes the specifications of terminal "2".
POINT
•Bias setting for 0 to 5VDC (0 to 10VDC) input
•Gain setting for 0 to 5VDC (0 to 10VDC) input
•Bias setting for 4 to 20mADC input
•Gain setting for 4 to 20mADC input
For 4 to 20mADC input, set "4" in any of Pr. 60 to Pr. 63 (input terminal
function selection) and assign AU (current input selection) to any of terminals
RH, RM, RL and STR, and turn on the AU signal.
Name
(Across
terminals 2-5)
Pr.73 *2
5V or 10V
)
(100% C4 )
Setting Range Factory Setting
1 to 120Hz
1 to 120Hz
0 to 60Hz
0 to 300%
0 to 300%
0 to 60Hz
0 to 300%
0 to 300%
60Hz
Factory setting
Pr.39
)
(
0Hz
C5
(
)
4mA
C6
) (100%
(20%
Frequency setting current signal
Use the calibration
parameter C2, C3 for setting
Use Pr. 38, calibration
parameter C4 for setting.
Use the calibration
parameter C5, C6
for setting.
Use Pr. 39, calibration
parameter C7 for setting.
27
60Hz
60Hz
0Hz
0% *1
96% *1
0Hz
20% *1
100% *1
(Across
terminals 4-5)
20mA
)
C7
5