Quick Start Guide
Standards
Markings:
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm with less than 1
mm thickness that forms a boundary between zone 0 (process
connection) and zone 1 (all other parts of the equipment).
The model code and datasheet are to be consulted for details
of the diaphragm material. Installation, maintenance, and
use shall take into account the environmental conditions to
which the diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be followed
in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic
build-up on painted surfaces and only clean the painted
surfaces with a damp cloth. If paint is ordered through
a special option code, contact the manufacturer for more
information.
I2 Brazil Intrinsic Safety
Certificate
Standards
Markings
Table 7-7: Input parameters
Voltage U
Current l
Power P
Capacitance C
Inductance L
34
UL-BR22.3807X (Singapore)
ABNT NBR IEC 60079-0, ABNT NBR IEC 60079-1,
ABNT NBR IEC 60079-26
Ex db IIC T6...T4 Ga/Gb IP66, T6 (–60 °C ≤ Ta ≤ +70
°C), T4/T5 (–60 °C ≤ Ta ≤ +80 °C)
UL-BR 14.0759X
ABNT NBR IEC 60079-0: 2013; ABNT NBR IEC
60079-11: 2013
Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +70 °C)
HART
30 V
i
200 mA
i
1 W
i
12 nF
i
0
i
Fieldbus/PROFIBUS
®
30 V
300 mA
1.3 W
0
0
October 2023
®