Table 5-2: Pressure Configuration via Class 2 Master
Steps
Set blocks to Out of Service Put Transducer Block into Out of Service mode
 
Select Measurement Type
Select Units
Enter Scaling
 
 
 
 
Set blocks to Auto
 
5.4 
Host integration
5.4.1  Control host (Class 1)
The Rosemount 2051 device utilizes condensed status as
recommended by the Profile 3.02 specification and NE 107. See
Rosemount 2051
assignment information.
The appropriate GSD file must be loaded on the control
host - Rosemount 2051 specific (rmt3333.gsd) or Profile 3.02
Generic (pa139700.gsd). These files can be found on
Rosemount
5.4.2  Configuration host (Class 2)
The appropriate DD or DTM file must be installed in the configuration
host. These files can be found at Emerson.com/Rosemount.
Quick Start Guide
for steps to configure the transmitter for Pressure
Actions
Put Analog Input Block into Out of Service mode
Set Primary Value type to Pressure
Set Engineering Units
Set Scale In in Transducer Block to 0–100
Set Scale Out in Transducer Block to 0–100
Set PV Scale in Analog Input Block to 0–100
Set Out Scale in Analog Input Block to 0–100
Set Linearization in Analog Input Block to No
Linearization
Put Transducer Block into Auto mode
Put Analog Input Block into Auto mode
Reference Manual
or Profibus.com.
Reference Manual
Primary and secondary units must match
for condensed status bit
Quick Start Guide