Download Print this page

Emerson Rosemount 2051 Series Quick Start Manual page 10

Flow meter
Hide thumbs Also See for Rosemount 2051 Series:

Advertisement

Quick Start Guide
Figure 1-3: O-rings
A. Flange adapter
B. O-ring
C. PFTE based
D. Elastomer
NOTICE
Replace PTFE O-rings if you remove the flange adapter.
1.7 
Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit
is required to provide a water/dust tight conduit seal and meets
requirements of NEMA
other Ingress Protection ratings are required.
For M20 threads, install conduit plugs to full thread engagement or
until mechanical resistance is met.
1.8 
In-line gauge transmitter orientation
The low side pressure port (atmospheric reference) on the in-line
gauge transmitter is located in the neck of the transmitter, behind
the housing. The vent path is 360° around the transmitter between
the housing and sensor.
(See
Figure
Keep the vent path free of any obstruction, including but not limited
to paint, dust, and lubrication by mounting the transmitter so fluids
can drain away.
10
Type 4X, IP66, and IP68. Consult factory if
®
1-4.)
October 2023
Emerson.com

Advertisement

loading

This manual is also suitable for:

Rosemount 2051cf seriesRosemount 2051Rosemount 2051 cf