Troubleshooting - Honeywell CENTRALINE EAGLE User Manual

Table of Contents

Advertisement

EAGLE CONTROLLER
Power LED Behavior
1
ON
2
OFF
LED Behavior
1
LED remains OFF after
power-up
2
LED is lit continuously after
power-up
3
LED flashes continuously
with following pattern:
4 x ON/OFF followed by
pause
4
LED flashes continuously
with following pattern:
7 x ON/OFF followed by
pause
RS485-1 LED Behavior
1 Both LEDs are flashing
2 Both LEDs are OFF
3 Rx Led is flashing and Tx is
OFF
4 Tx Led is flashing and Rx is
OFF
The power and status LEDs at the EXCEL WEB II controller indicate the controller´s
statuses and allows troubleshooting. Please refer to the following tables that
describe the behavior, meaning and necessary action to check status and solve
errors and/problems.
Power LED (green)
Meaning
Normal operation
Power supply not OK
Status / Alarm LED (red)
Meaning
Normal operation
The controller has encountered a hardware
problem or
The application has a fault or
The controller has been powered up without an
application or
The operator has manually stopped the
application, e.g., using XW-Online. In this case,
the LED will light up 13 minutes after power-up
without application
Sensor failure of analog input
Communications failure on Panel Bus
RS485-1 Send (Tx) / Receive (Rx) LED (yellow)
Meaning
Normal operation, RS485-1 is functioning
properly
No RS485-1 communication
RS485-1 communication is switched off but
controller is receiving data from other controllers
Controller is trying to establish a RS485-1
connection but there is no answer
,
Application LEDs (yellow)
NOTE:
The LED can be used to display application-dependent status information
like "Cooling Mode", "Heating Mode", "Service Interval" etc.
Action
No action necessary
Check power supply voltage / wiring
Service Action
 No action necessary
 Try powering down and then
 If problem persists, check and – if
 If problem still persists, replace
 Check sensor or connection
 Check analog input configuration
 Check bus wiring
 Check for incorrect HEX addresses
Action
 No action necessary
 Check RS485-1 termination switch
 Switch on RS485-1 communication
 RS485-1 baud rate is not correct;
80
TROUBESHOOTING

TROUBLESHOOTING

powering up the XCL8010.
necessary – reload the application.
hardware
(2 Panel Bus IO modules using
same HEX address)
via the CARE PC tool. Hardware
may be defect if this does not work
other controller may have the same
device number on RS485, wiring
problem or hardware defect