TROUBLESHOOTING

Binding and configuring issues

1. You can't Bind the L510 from EngINN. The "Bind" button is disabled
Possible Reasons:
Configure EngINN to connect to WSCon instead of the PC503. Look in the lower right corner of EngINN. If you see "Server
(WSCon), configure EngINN to connect to the WSCon program instead of the PC503. Click the "Server (WSCon)" item to open a
Settings window. From there, set the EngINN Communication. Interface to PC503 instead of Server (WSCon) and click the Save
button to update EngINN.
2. You can't Bind the L510 from EngINN. When Binding the L510 from EngINN, you click the Reverse Bind Start button, then
go to the L510 and press its Bind button, but EngINN never indicates it received a Bind request and never displays a Green
check or indicates the device is Online.
INCOMM L510 LAMP CONTROLLER USER GUIDE
11
v1.5 October 26, 2022
31-00593-01